Home › Blog › Electromechanical & Switchgear › Busbar, Transformer & Motor Insulation › Creepage, clearance, and CTI
Creepage, Clearance, and CTI: Why Switchgear Phase Barriers Track, and How Spacing Design Prevents It
By the H-O Products applications engineering team · Updated June 2026 · ~8 min read
Most field insulation events in switchgear are creepage-path events: contamination, condensation, and tracking along a surface, not puncture through the material. That sentence from the parent application page reframes how barrier materials should be chosen. The bulk dielectric number on a TDS describes puncture, the failure that rarely happens; the comparative tracking index describes the surface, where the real failures live.
This article walks the two distances, the IEC 60664-1 framework that ties them to working voltage and environment, the CTI material groups per IEC 60112, and the two spacing failures the parent page catalogs from the field.
Request a quote for your project →
Two distances, two different physics
Clearance is the shortest distance between two conductive parts through air; creepage is the shortest path between them along insulating surfaces. They fail differently: clearance flashes over in one event, while creepage degrades progressively as contamination and humidity let leakage current carbonize a track, millimeter by millimeter, until a phase-to-phase flashover finishes the job.
IEC 60664-1 tabulates required values for both from the working voltage, the overvoltage category, the pollution degree, and the material group, and they are different numbers solving different physics.
MV gear layers IEC 62271 and IEEE C37.20 requirements on top.
CTI: the property that buys back distance
The comparative tracking index, per IEC 60112, ranks how well an insulating surface resists forming a carbonized conductive track under contamination and voltage. IEC 60664-1 sorts materials into groups by CTI, Group I at CTI ≥ 600 down through Group IIIb (100 ≤ CTI < 175), and allows shorter creepage for higher groups at the same voltage and pollution degree.
That is the mechanism by which a tracking-resistant composite or an inorganic mica barrier earns its price on a tight MV layout: it buys back distance the layout does not have. Two cautions from the parent page: verify the CTI group of the actual grade on its TDS, because groups differ between grades of one family, and remember that mica does not carbonize at all, which is half of why it owns the arc-adjacent zones.
The Two Spacing Failures and the Design Response
| Field failure | Mechanism | Design response |
|---|---|---|
| Tracking across a contaminated barrier | Barrier sized for clean, dry air; service delivered conductive dust and condensation cycles; leakage carbonized a track and finished with flashover | Match the material group to the real pollution degree: tracking-resistant composite (IEC 60112 data on the Durostone TDS) or inorganic mica for dusty, damp, or outdoor-adjacent gear |
| Creepage measured as a straight line | The 25 mm between phases was read as both clearance and creepage; the surface path through standoffs, barrier faces, and grooves was far shorter once hardware landed; the gear passed dry and failed wet | Trace the actual surface path in CAD, use barrier geometry deliberately, and read both required values from the IEC 60664-1 tables for the working voltage, overvoltage category, and pollution degree |
Patterns as cataloged on the parent application page. The binding spacing values live in the IEC 60664-1 tables applied to your design; this article quotes none.
A phase barrier is creepage engineering
A barrier earns its keep by forcing the creepage path around itself: the surface distance over the top and around the edges of a glass-epoxy or Durostone plate is the design quantity, which makes barrier geometry spacing design, not just material choice. That is also why the conversion details matter.
H-O waterjet-cuts laminate barriers with clean, delamination-free edges, because fiber pull-out and micro-cracks at edges and fastener holes are moisture paths and stress risers in exactly the surface the creepage calculation counts on; edge quality and burr limits belong on the print as conversion specifications.
The discipline: pick the barrier with the tables open
Insulation is coordinated, not just selected. IEC 60664-1 ties working voltage, pollution degree, and material group together: change one and the required spacing changes.
The parent page's specification principle is to pick the barrier material with the spacing tables open, not after the layout is frozen, because the choice between a Group III laminate and a higher-CTI surface is exactly the choice between carrying the tabulated distance and shortening it.
For sheltered, conditioned gear, standard laminates carry the duty economically; for dusty, damp, or outdoor-adjacent compartments, the tracking-resistant composite and the inorganic families are what keep the surface story intact for decades. Aramid paper and polyimide film carry the same coordination logic into windings and slots, where the system's thermal class (IEC 60085, UL 1446) joins the spacing story.
How H-O Products helps
H-O Products is a precision converter, not a design authority and not a raw-material producer. We do not derive your required creepage and clearance; those come from the IEC 60664-1 tables applied to your design.
What we do is converse with that calculation: recommend a barrier family whose CTI group, per its TDS, supports your material-group assumption; convert the barrier geometry that delivers your surface path, waterjet-cut with clean edges; laminate mica to structural backings where arc zones demand inorganic surfaces; and supply material traceability with lot-code TDS records under our ISO 9001:2015 certified quality management system.
Frequently asked questions
What is the difference between creepage and clearance?
Clearance is the shortest distance between two conductive parts through air; creepage is the shortest path between them along insulating surfaces. They fail differently: clearance flashes over in one event, creepage degrades progressively as contamination and humidity let leakage current carbonize a track. IEC 60664-1 tabulates required values for both from the working voltage, overvoltage category, pollution degree, and material group. Trace the real surface path in CAD, not the straight line.
What is CTI and why does it change my required spacing?
The comparative tracking index, per IEC 60112, ranks how well an insulating surface resists forming a carbonized conductive track under contamination and voltage. IEC 60664-1 sorts materials into groups by CTI (Group I at CTI ≥ 600 down to Group IIIb) and allows shorter creepage for higher groups at the same voltage and pollution degree. Verify the CTI group of the actual grade on its TDS; it differs between grades of one family.
Why is mica treated differently from laminates in tracking-critical zones?
Because mica's inorganic surface does not carbonize: there is no organic binder path for a track to grow along, which is why arc-rated muscovite owns MV phase barriers and arc chutes and phlogopite extends the duty into extreme-temperature zones per the maker's designations. Organic laminates, even good ones, are ranked by how well they resist tracking; mica sidesteps the mechanism. The trade is brittleness, handled by laminating mica to a structural backing, converted as one part.
Can H-O calculate the creepage and clearance my design needs?
No; those values come from the IEC 60664-1 tables applied to your working voltage, overvoltage category, pollution degree, and material group, and they belong to your design authority, with IEC 62271 and IEEE C37.20 layered on for MV assemblies. What we do is support the calculation: recommend families whose TDS-cited CTI fits your material-group assumption, convert barrier geometry that delivers the surface path, and document the material with the order.
Have the barrier geometry reviewed against your spacing requirement
Send the layout with the working voltage, pollution degree, and any required creepage and clearance verbatim, and we will recommend a barrier family whose tracking class supports the design.
Samples typically ship in 3 to 5 business days for common die-cut configurations on materials we keep on hand; standard production runs about two weeks after drawing approval; expedited service is available. MOQ varies by material and part.
Family-owned in Winsted, Connecticut since 1971 · ISO 9001:2015 certified · OEMs worldwide send us a drawing — and get back their part.
Related reading
Request a quote for your busbar, transformer & motor insulation part
Send H-O your drawing or describe the part—engineering reviews every RFQ and converts samples on your geometry.
Last updated · Reviewed by H-O Products engineering (ISO 9001:2015 certified converter, Winsted, CT).
References
- IEC 60664-1 (insulation coordination: creepage and clearance from working voltage, overvoltage category, pollution degree, and material group).
- IEC 60112 (comparative tracking index, the CTI behind the material groups); IEC 60243 (electric strength); IEC 60270 (partial discharge, cited on the APTIV XPI TDS).
- IEEE C37.20 and IEC 62271 (the switchgear assembly standards layered on MV designs); IEC 60085 and UL 1446 (thermal class and insulation systems).
- Manufacturer technical data sheets: Durostone composite (IEC 60112 tracking data), glass-epoxy laminates, muscovite and phlogopite mica, APTIV PEEK films.
This article explains spacing and tracking concepts for switchgear insulation using the frameworks and materials cited on the parent application page. No creepage, clearance, or CTI value is stated for any design or grade beyond the standard's own group definitions; the binding distances come from the IEC 60664-1 tables applied to your design, and grade-level CTI values must be read from the manufacturer's current technical data sheet.
All parts are custom manufactured to order; minimum production run quantities vary by material and part. H-O is a converter, not a raw-material producer, and does not certify finished switchgear.