Doc No GC-DPT-01 Rev 1.0 Updated 2026-07 Document Application Page · Duct, Pipe & Thermal Insulation Classification Public Release
Custom Die-Cut Duct & Pipe Insulation Parts · For mechanical & insulation contractors and MEP designers

Duct, Pipe & Thermal Insulation

H-O Products die-cuts and converts the flexible-insulation and gasket parts that keep a building's duct and pipe distribution thermally sound and condensation-free: closed-cell elastomeric (EPDM and nitrile) collars, wraps, and saddle pieces for below-dew-point chilled-water, refrigerant, and condensate lines; thermal and acoustic duct-liner die-cuts for supply and return plenums; duct-flange and connection gaskets and closure strips; and thermal-break pads at pipe supports and penetrations, built to your drawing.

Built for: chilled-water and refrigerant lines fighting condensation and corrosion-under-insulation, supply and return ductwork needing thermal and sound-absorbing liner, dual-temperature duct that needs a continuous vapor boundary, and the sheet-metal connection joints that leak air and vapor, with every material class cited by designation and every value per the vendor TDS.

01
8 families
Insulation & gasket material families on this page
Closed-cell elastomeric EPDM and nitrile, glass-fibre duct liner and paper, silicone foam, neoprene, PE foam, PTFE-coated glass, and the low-perm vapor-retarder facings, each converted to drawing.
02
6 jobs
Numbered duct-and-pipe jobs, drawing-ready
Below-dew-point pipe, hot / process pipe, duct thermal-and-acoustic liner, duct external wrap, duct connection gaskets and closures, and pipe-support thermal breaks, each with what-to-send notes.
03
25/50
The flame-spread / smoke-developed index pair for ducts and plenums
Materials in ducts and plenums commonly need a 25/50 index (flame-spread ≤25, smoke-developed ≤50) per ASTM E84 (UL 723) testing on the vendor TDS; NFPA 90A governs the location, and the index belongs to the tested material grade.
04
16
Cited standards, methods & technical references
ASTM C534, C1071, C1136, C177/C518, E96, E84, C411, UL 723/181/94, D1056, and the NFPA 90A context: material values per the vendor TDS, code compliance and system ratings by designation only.
LocationMade in Winsted, CT · Family-owned since 1971 · ISO 9001:2015 Certified Organization
Commercial building mechanical room with insulated chilled-water piping and sheet-metal ductwork wrapped in thermal and acoustic insulation, the application context for duct and pipe insulation parts
Quick Answer

To spec insulation for a building’s duct and pipe distribution, work from the service condition. On cold (below-dew-point) pipe the job is condensation control, not R-value alone: pick a closed-cell elastomeric EPDM foam — or nitrile where oil resistance or cost drives — whose low water-vapor permeance (ASTM E96) is the built-in vapor retarder, and size the wall to keep the surface above the design dew point.

Duct-liner, hot-pipe, and connection duties are mapped in the When-to-spec list on this page. Values are per the TDS on file; see the material reference below for ordering details.

Standards & Test Methods

Material specs and methods, per the maker TDS: ASTM C534 (flexible elastomeric cellular insulation) · ASTM C1071 (fibrous glass duct liner) · ASTM C1136 (low-permeance vapor-retarder facings) · ASTM C177 (guarded hot plate, k) / ASTM C518 (heat flow meter, k) · ASTM E96 (water-vapor transmission, perm) · ASTM E84 / UL 723 (surface burning, flame-spread and smoke-developed) · UL 181 (duct-liner erosion / service velocity) · UL 94 (plastic flammability, V-0) · ASTM C411 (hot-surface performance) · ASTM D1056 (cellular-rubber class).

Installation-level, by designation (belongs to the building): NFPA 90A / 90B (25/50 for duct and plenum materials).

When To Spec What
Finished die-cut Closed-Cell Elastomeric EPDM Foam parts converted by H-O Products, on release liner ready to ship
How it works
  1. 1
    Send drawing
    Upload a DXF, STEP, or PDF, or describe the pipe run, duct size, or connection and the service conditions. A sample fitting works too.
  2. 2
    Material review
    Engineering reviews the service temperature, the design dew point on cold lines, and any fire-class requirement, then frames the standards honestly: material classes (k per ASTM C177/C518, permeance per E96, the E84 25/50 index, ASTM C534/C1071 conformance) per the maker TDS; the code compliance and the system rating belong to the installed building.
  3. 3
    Prototype
    Samples typically ship in 3–5 business days for common configurations in commonly converted materials. Made-to-order; MOQ varies by material and part.
  4. 4
    Production
    Standard production runs ship about 2 weeks after drawing approval, on flatbed die-cutting, CNC knife cutting, and kitting for laminated foam-and-facing and collar-and-closure sets. Ongoing parts run with material traceability and lot-code TDS records.
Prototype-to-Production Insulation Part Manufacturing · Duct & Pipe Insulation Converting

Condensation or thermal problem → service & dew point → material selection → converted part → production supply.

  1. 1
    Name the line or duct & service
    Chilled water, refrigerant, condensate, hot water, or supply/return duct, with its service temperature and (cold service) the design dew point.
  2. 2
    Set thermal & vapor requirement
    On cold service, size the wall to hold the surface above the dew point and pick a low-permeance material as the vapor retarder; on hot service, target the skin temperature.
  3. 3
    Set the fire class
    Confirm any 25/50 flame-spread / smoke-developed requirement for a duct or plenum location per ASTM E84, per the material TDS.
  4. 4
    Choose the material
    Match the family to service, exposure (indoor / outdoor / wash-down), and duct-liner air velocity, and add the vapor-retarder facing where it is needed.
  5. 5
    Die-cut to drawing
    Die-cut, waterjet-cut, slit, laminate, and kit the collars, wraps, liner pieces, gaskets, and closures to the run.
  6. 6
    Quote prototype or production
    Prototype quantities through full production runs, with the TDS and lot-code traceability behind the part.
Who this is for

This guide is for mechanical and insulation contractors, MEP and mechanical designers, and building owners specifying die-cut duct and pipe insulation and gasket parts for a building's HVAC and plumbing distribution — chilled-water and refrigerant lines, supply and return ductwork, and their connection joints.

If your problem is the thermal layers inside a packaged HVAC appliance on the OEM line (heat exchanger, burner-adjacent, cabinet thermal break), that is the equipment side and the HVAC-OEM thermal page; this page is the installed building's duct and pipe runs.

Fire-stopping at rated penetrations is the fire, life safety & smoke control sibling.

Converted Duct & Pipe Insulation Parts · Where it lives

Application Zones

Six insulation problems define this page: below-dew-point pipe fighting condensation; hot and process pipe managing skin temperature; ductwork needing a thermal and acoustic liner; duct needing an external thermal wrap and, on cold service, a vapor boundary; the sheet-metal connections that leak air and vapor; and the pipe supports and penetrations where a thermal-break part belongs.

In every one, the part answers to the service condition first: on the cold side, the dew point and the vapor drive inward; on the hot side, the skin temperature; in a duct, the fire class and the air velocity.

Click a tab to see the duty, the controlling properties, and the families H-O converts for that zone.

Below-dew-point pipe cross-section: vapor drives inward Concentric cross-section of a cold pipe. The metal pipe is at the center, wrapped in a closed-cell elastomeric insulation wall of a design thickness. The ambient dew-point isotherm is drawn as a dashed ring inside the insulation wall. Water-vapor drive arrows point inward, from the warm humid room toward the cold pipe, opposite to the outward heat direction on a hot line. The teaching point is that the wall must be thick enough, and its vapor boundary continuous enough, to keep the whole cross-section and the outer surface above the dew point. Qualitative, no numeric values. COLD-SERVICE PHYSICS · VAPOR DRIVES TOWARD THE COLD PIPE On a below-dew-point line, insulate for vapor drive, not just heat Keep the whole insulation cross-section, and its outer surface, above the design dew point, and keep the vapor boundary continuous at every fitting. COLD PIPE Closed-cell elastomeric wall Low water-vapor permeance (ASTM E96) is the built-in vapor retarder; k per ASTM C177 / C518. Dew-point isotherm (dashed) Must stay inside the wall; if the surface reaches it, the pipe sweats and wets the insulation. Vapor drives inward Warm humid air pushes moisture toward the cold pipe, so seams, collars, and terminations must seal vapor-tight. Representative — validate in the application.
Figure: qualitative cross-section of a below-dew-point pipe wrapped in closed-cell elastomeric insulation. Unlike a hot line, the vapor drive runs inward toward the cold pipe, so the wall must be thick enough to hold the surface above the design dew point and the vapor boundary must be continuous at every fitting. Geometry and layer count are illustrative; validate the wall thickness against the project dew point and the vendor thickness tables. [1]

Tip: on cold service the weakest 5% of the surface governs. A perfect wrap with an unsealed collar at a valve or an open seam lets vapor bypass the good material, condense on the cold metal, and start corrosion-under-insulation, which is why the fitting collars and closures are parts, not field offcuts.

Chilled-water piping in a mechanical room insulated with closed-cell elastomeric foam, with sealed seams and fitting collars at the elbows and valves

Below-dew-point pipe: control condensation, not just heat gain

Controlling requirement: keep the surface above the design dew point; vapor drives inwardMaterial methods: ASTM C534, C177/C518, E96

Chilled-water, refrigerant-suction, and condensate lines run for the building's life below the surrounding dew point, so the design problem is condensation, not R-value alone. On a surface below the dew point, water vapor is driven inward toward the cold pipe, so the insulation has to do two things at once: slow the heat gain (thermal conductivity per ASTM C177/C518) and resist that vapor drive along its whole thickness (water-vapor permeance per ASTM E96) behind a continuously sealed boundary.

Closed-cell elastomeric foam is the workhorse because its own low permeance is the built-in vapor retarder, so a correctly sized and sealed wall needs no separate wrap in most indoor runs; EPDM is the weather-tolerant default and nitrile the oil-resistant, economical option. The thickness comes from the vendor condensation-control table for the design pipe temperature, ambient temperature, and relative humidity, and the fitting collars, seams, and terminations are and sealed so the weakest 5% of the surface does not become the sweat point.

Send the line service temperature and the design dew point, and the material class and thickness follow.

Closed-Cell Elastomeric EPDMChilled-water and refrigerant collars and wraps; low water-vapor permeance is the built-in vapor retarder, thermal conductivity per ASTM C177/C518, spec per ASTM C534. [1]
Closed-Cell Nitrile (NBR)Economical, oil-resistant closed-cell wrap and collar for refrigeration and mechanical-room cold lines; permeance per ASTM E96, cellular class per ASTM D1056. [6]
Low-Perm Vapor-Retarder FacingWhere a faced jacket is specified on cold service, the facing and its sealed seams carry the vapor boundary; facing spec per ASTM C1136, perm per ASTM E96. [3]
Crosslinked PE FoamEconomical closed-cell pipe collars and thermal spacers on cold and warm lines; closed-cell structure resists moisture uptake, class per the maker TDS. [13]

Hot & process pipe: skin temperature and, in a plenum, the fire class

Controlling requirement: heat loss / skin temperature; fire class where the location demands itMaterial methods: ASTM C411, E84, UL 94

Heating hot-water, steam-condensate, and domestic-hot-water lines run the other direction: the vapor drive is outward and the concern is heat loss and personnel-protection skin temperature. The material choice moves toward the higher-temperature families.

Closed-cell elastomeric grades cover the moderate range (the AP-class elastomerics are tested to about 250 °F for hot-surface performance per ASTM C411), and where the line runs hotter or through a plenum, glass-fibre and silicone-foam grades carry the temperature and, importantly, the fire class: materials in a duct or plenum location commonly need a 25/50 flame-spread / smoke-developed index per ASTM E84, with a UL 94 V-0 class on any plastic-foam grade used there.

Frame the service temperature and the required fire class for the location, and the family and thickness follow, with the E84 index read off the grade TDS.

Silicone Foam (BISCO® HT/BF)Hot-line and plenum insulation and gaskets across the widest temperature range with UL 94 V-0 grades; classes per the maker TDS, E84 index where reported. [12]
Glass-Fibre Paper & SheetHigh-temperature glass-fibre insulation and gasket paper for hot pipe and equipment; inorganic and non-combustible, surface burning per ASTM E84 on the TDS. [7]
Closed-Cell ElastomericModerate hot-line wrap where the service temperature stays inside the elastomeric range; hot-surface performance per ASTM C411, spec per ASTM C534. [11]
PTFE-Coated FibreglassHigh-temperature, low-friction gasket and facing at hot joints and slip points; PTFE-coated glass cloth, temperature range per the maker TDS.
Interior of rectangular sheet-metal supply ductwork lined with fibrous-glass duct liner for thermal and acoustic performance, cut cleanly at the seams

Duct thermal & acoustic liner: thermal, quiet, and erosion-resistant

Controlling requirement: thermal + sound absorption; erosion at the system air velocity; 25/50 fire classMaterial methods: ASTM C1071, UL 181, E84

Supply and return ductwork and plenums are lined to do two jobs at once: cut the conductive heat gain or loss through the sheet metal, and absorb the fan and airflow noise before it travels the duct. Fibrous-glass duct liner is the standard here, and ASTM C1071 is the specification that catalogues what it must do: apparent thermal conductivity, sound-absorption coefficients, erosion resistance, water-vapor sorption, and combustion characteristics, for air up to 250 °F.

Two numbers govern the selection: the sound and thermal duty (from the acoustic and energy design) and the system's air velocity, because the liner surface has to withstand that velocity without eroding or shedding fibres, verified per UL 181. A closed-cell foam liner is the alternative where a wipeable, non-fibrous surface is required (labs, healthcare, wash-down). The matters at the edges: cleanly cut, sealed liner edges do not fray into the airstream, which is where an unfaced field cut starts to erode.

Send the duct dimensions and the design air velocity, and the liner and its edge treatment follow.

Fibrous-Glass Duct LinerThermal-and-acoustic interior duct liner; apparent k, sound absorption, and erosion per ASTM C1071 and UL 181, surface burning per ASTM E84 on the TDS. [2]
Closed-Cell Foam Liner (wipeable)Non-fibrous closed-cell liner where a cleanable surface is required; class and temperature per the maker TDS, E84 index where reported. [7]
Facings & Edge TreatmentsFaced and edge-coated liner constructions that seal the cut edge against erosion and, on cold duct, carry the vapor boundary; facing per ASTM C1136. [3]
Acoustic Felt InsertsPressed-felt inserts for targeted sound damping at specific duct sections and equipment transitions; density and thickness per the maker TDS. [16]

Duct external wrap: thermal wrap and, on cold duct, a vapor boundary

Controlling requirement: heat gain/loss through the duct wall; vapor boundary on cold/dual-temperature ductMaterial methods: ASTM C177/C518, E96, C1136

Where the duct is not lined, or where an additional thermal layer is wanted on the outside, an external wrap carries the thermal duty. On warm-air duct in an unconditioned space, the wrap is a straightforward R-value part; on cold or dual-temperature supply duct running through humid or unconditioned space, it is a condensation problem just like a cold pipe, and the wrap needs a low-perm facing (ASTM C1136) as its vapor boundary, sealed continuously at the seams and the sheet-metal joints.

Closed-cell elastomeric and PE foam wraps bring their own low permeance; faced fibrous-glass wrap uses the facing as the boundary. The parts here are the corner pieces, the collars at takeoffs and dampers, and the closure strips at the transverse joints, the places a continuous wrap cannot cover by itself. Send the duct size and whether the service is cold, warm, or dual-temperature, and the wrap and its facing follow.

Closed-Cell Elastomeric WrapCold and dual-temperature duct wrap with built-in low permeance; thermal conductivity per ASTM C177/C518, spec per ASTM C534. [1]
PE Foam Wrap & SpacersEconomical closed-cell duct wrap, corner pieces, and thermal spacers; closed-cell structure limits moisture uptake, class per the maker TDS. [13]
Vapor-Retarder Facing & ClosuresThe vapor boundary on faced fibrous-glass duct wrap and the closure strips at joints and takeoffs; facing per ASTM C1136, perm per ASTM E96. [3]
Expanded PE Corner & Collar PartsDie-cut expanded-PE corners, takeoff collars, and damper collars that cover what a continuous wrap cannot; class per the maker TDS.

Duct connection gaskets & closures: stop the air and vapor leakage at the joint

Controlling requirement: seal the sheet-metal connection against air and vapor leakageMaterial methods: ASTM D1056, D2240, E84

A duct system leaks at its connections, and on cold service every connection is also a vapor path. Transverse-flange joints (companion-flange and slide-on-flange systems), slip-and-drive connections, access-door and plenum joints, and equipment transitions all take a gasket, and the gasket has two jobs: seal the air leakage that wastes fan energy, and, on cold duct, close the vapor boundary across the joint.

Die-cut closed-cell foam gaskets sized to the flange closure force and gap are the workhorse: neoprene for general weather-and-oil duty, EPDM where UV and ozone or a wet exposure dominate, and silicone foam where the joint runs hot or needs a UL 94 flame class. Where a solid strip suits the joint, solid EPDM or a PTFE-coated glass facing takes the high-temperature or slip-point duty.

Send the flange or connection detail and the gap, and the gasket construction and its class follow.

Closed-Cell Neoprene GasketsTransverse-flange, slip-and-drive, and access-door gaskets; good weather and oil resistance at foam closure forces, cellular class per ASTM D1056. [13]
Solid EPDM & EPDM FoamSolid and closed-cell EPDM gaskets and closure strips where UV, ozone, or a wet exposure drives; EPDM foam at the joint, durometer per ASTM D2240. [13]
Silicone Foam GasketsConnection gaskets where the joint runs hot or needs a UL 94 flame class; widest temperature range, classes per the maker TDS. [12]
PTFE-Coated Glass FacingsHigh-temperature, low-friction gasket and slip facing at hot transitions and expansion joints; PTFE-coated glass cloth, range per the maker TDS.

Supports, hangers & penetrations: the thermal break at the metal contact

Controlling requirement: break the thermal bridge at supports; protect the insulation at penetrationsMaterial methods: SAE J314 / maker TDS, ASTM D1056

The last places a duct or pipe loses its insulation value are the metal-to-metal contacts: the pipe hanger or clamp that bridges straight through the insulation to the cold or hot pipe, the support saddle, and the point where a line passes through a wall, floor, or roof. A thermal-break saddle or insert keeps the hanger from short-circuiting the insulation and, on cold lines, from becoming a local sweat point; a pressed-felt or closed-cell saddle also damps the support noise.

At penetrations, an insulation insert or sleeve carries the insulation cleanly through the opening and protects it from crushing. Fire-rated penetrations are their own discipline: the fire-stopping seal at a rated wall or floor belongs to the fire, life safety, and smoke-control sibling page; this zone is the thermal-break and support-protection part. Send the hanger or support detail and the pipe or duct size, and the saddle or insert follows.

Pressed-Felt Saddle PadsThermal-break and anti-vibration saddles at pipe hangers and supports; damps support noise and breaks the metal bridge, density per the maker TDS (SAE J314). [16]
Closed-Cell Elastomeric InsertsHanger inserts and support pieces on cold lines that carry the insulation through the clamp without a sweat point; low permeance, spec per ASTM C534. [1]
PE Foam Sleeves & InsertsDie-cut sleeves and inserts that protect the insulation where a line passes through an opening or a support; closed-cell, class per the maker TDS.
Fire-stopping at rated penetrations (sibling)The fire-rated seal at a penetration through a rated wall or floor is a tested-assembly job; it is covered on the fire, life safety & smoke-control sibling page.
Spec discipline

Six decisions that drive your duct & pipe insulation spec

A duct or pipe insulation part is a single-purpose part, and each of these decisions has one controlling property. Miss one and the failure is rarely immediate: a cold line starts to sweat months later, a plenum material has no fire class, a duct liner sheds into the airstream, or a vapor boundary is intact everywhere except the one fitting that governs.

Specification principle

Materials carry classes; the installed building carries the code compliance and the system rating. A thermal conductivity (k per ASTM C177/C518), a water-vapor permeance (per ASTM E96), and a 25/50 surface-burning index (per ASTM E84) belong to the tested material grade per its TDS. The NFPA 90A location requirement, the assembly's fire rating, and the finished condensation-control result belong to the installed building.

Write material classes on the part callouts, cite the standards by designation, and never let a drawing imply that a collar is "code-compliant" or "fireproof": it is a documented component of the installed system.

Dew point
The number that governs cold service, ahead of R-value alone

On a below-dew-point line the design target is to keep the whole insulation cross-section, and its outer surface, above the ambient dew point. Because vapor is driven inward toward the cold pipe, the wall must be thick enough and the vapor boundary continuous enough that the surface never falls to the dew-point isotherm.

Thickness comes from the vendor condensation-control table for the design pipe temperature, ambient temperature, and relative humidity; being short by as little as ~0.25–0.50 in. can start condensation even with a good material. [14]

Closed-Cell Elastomeric (EPDM) Vapor roleLow WV permeance = built-in retarder MethodsASTM C534; C177/C518; E96; C411 RoleCold pipe collars & wraps FormDie-cut collars / wraps / saddles

Read the six factors below in order. The first three govern the cold side (dew point and vapor drive, thermal conductivity and thickness, vapor-boundary continuity); the fourth sets the fire class for duct and plenum locations; the fifth matches a duct liner to its air velocity; the sixth matches the material to its exposure. Every factor names its test method, because in this application the documentation is part of the part.

Show all 6 selection factors tap to expand
1

Dew point and vapor drive: cold service is a condensation problem

Rule — on a below-dew-point line, design to keep the surface above the dew point and treat the low water-vapor permeance of a closed-cell elastomeric as the vapor retarder, not R-value alone. On a surface below the ambient dew point, vapor is driven inward toward the cold pipe, so the wall must both slow heat gain (k per ASTM C177/C518) and resist that vapor drive along its whole thickness (permeance per ASTM E96).

Send the line service temperature and the design dew point (or ambient temperature and relative humidity), and the material class and the thickness from the vendor condensation-control table follow. [6]

R-value alone is a hot-service habit: on the cold side, permeance and the continuity of the seal govern.
2

Thermal conductivity and thickness: size to the condition, not a generic table

Rule — pick the wall thickness from the design condition, not a one-size table, and cite k with its method and mean temperature. Thermal conductivity (k) is measured per ASTM C177 (guarded hot plate, reference/precision) or ASTM C518 (heat flow meter, production QA), and it rises with temperature, so a k value only means something with its stated mean temperature.

On cold service the thickness is set by the dew-point table; on hot service by the target skin temperature. State the service temperature and (cold) the design dew point; being short by ~0.25–0.50 in. can drop the surface below dew point even with the right material. [4]

A k number without its mean temperature is not a spec: thin margins on thickness are where cold lines start to sweat.
3

Vapor-boundary continuity: the weakest 5% of the surface governs

Rule — seal the vapor boundary continuously at every seam, fitting, and termination, and make the fitting collars and closures parts, not field offcuts. A correctly sized wall fails anyway if vapor bypasses it at the collar on a valve, an elbow, or an open seam; that is where vapor reaches the cold metal, condenses, wets the insulation, collapses its R-value, and starts corrosion-under-insulation.

On faced systems the facing (ASTM C1136) and its sealed seams carry the boundary. Call out the fittings and terminations and let H-O the collars, saddles, and closures so the boundary is continuous where it is weakest. [3]

The good material at 95% of the surface does not matter if the last 5% at the fittings is open.
4

Fire class: 25/50 where the duct or plenum location demands it

Rule — confirm the fire class the location requires and read the index off the grade TDS. Materials in ducts and plenums commonly need a 25/50 surface-burning index (flame-spread ≤25, smoke-developed ≤50) per ASTM E84 (UL 723), the requirement NFPA 90A/90B set for those locations, and a UL 94 V-0 class on any plastic-foam grade used there.

The index is a material class on the grade TDS; the code compliance and the assembly rating belong to the installed building. Name the location (duct, plenum, exposed) and any 25/50 requirement, and the family follows. [7]

The 25/50 index belongs to the tested grade; the NFPA 90A compliance belongs to the installed system.
5

Duct-liner erosion: match the liner to the system air velocity

Rule — match the duct liner and its edge treatment to the system's air velocity so it does not erode or shed fibres. A fibrous-glass duct liner (ASTM C1071) is defined by apparent thermal conductivity, sound-absorption coefficients, erosion resistance, water-vapor sorption, and combustion characteristics, and its surface must withstand the service velocity without eroding, verified per UL 181. A cleanly die-cut, sealed edge does not fray into the airstream, which is where an unfaced field cut starts to erode.

Send the duct dimensions and the design air velocity, and the liner and its edge treatment follow. [2]

A liner rated below the service velocity erodes and sheds; the edge is where erosion begins.
6

Exposure: match the elastomer and facing to indoor, outdoor, or wash-down

Rule — match the material and its facing to the real exposure, not just the thermal duty. EPDM is the weather- and UV-tolerant default where duct or pipe runs exposed outdoors; nitrile is the oil-resistant, economical option indoors; silicone foam covers the widest temperature range and hot joints; and a facing has to survive a wet mechanical-room or wash-down area without failing.

A foam or facing that hardens under UV, or an incompatible facing in a wash-down zone, is a material-to-exposure mismatch, not a thermal error. Name the exposure (indoor / outdoor / wash-down) and any UV or oil contact, and the family and facing follow. [1]

Exposure picks the elastomer as surely as service temperature does: UV, oil, and wash-down each rule some families out.
Decision support
Instrumentation·Interactive Selection

Specification Tools

Two tools to take you from "we're insulating a chilled-water run" to here's the part checklist for the drawing set: a requirement-driven insulation-part builder that assembles the collar, wrap, liner, gasket, and closure layers with their citations, and a side-by-side comparison of every insulation and gasket family on this page.

1. Duct & pipe insulation-part checklist builder

Check the requirements your line, duct, or connection carries. The builder assembles the corresponding collar, wrap, liner, gasket, and closure layers into a checklist with the family, what to send with the drawing, and the citation language (material classes per TDS; code compliance and the system rating belong to the installed building). The default selection below is pre-built for a typical below-dew-point chilled-water run; every layer is also printed in the material reference section, so nothing here exists only behind a script.

Part checklist: 2 layers selected

Each checked requirement adds its layer below. The list is the starting bill of materials for the engineering review, not a certification: material classes (k per ASTM C177/C518, permeance per E96, the E84 25/50 index) come from the grade TDS, and the code compliance and the system/assembly rating belong to the installed building.

    Copy line for the RFQ: "Duct & pipe insulation part set, 2 layers. Cold-service thickness sized to the design dew point per the vendor table; material classes per TDS; code compliance and system rating belong to the installed building."
    The builder assembles converter-side layers only. It does not size the wall thickness for you, design the duct system, or certify a fire or condensation-control result; the dew-point sizing, the fire class of the location, and the finished performance belong to the installed building and the vendor thickness tables. H-O supplies the layers, the TDSs, and lot-code traceability behind them.

    2. Side-by-side: insulation & gasket family comparison matrix

    Every family called out on this page, with construction, the property that drives its selection, the material-level methods its TDS cites, and the zone it serves. Click a column header to sort. Click any material name to jump to its accordion entry. Code compliance and system ratings are not in this table because they belong to the installed building, not the material.

    Filter
    Material Construction Selection driver Material methods on the TDS Zone
    Cold-service insulation (condensation control)
    Closed-Cell Elastomeric EPDMEPDM foam (sheet/tubular) Closed-cell EPDM foam Low WV permeance (vapor retarder) ASTM C534; C177/C518; E96; C411 Cold pipe, dual-temp duct
    Closed-Cell Nitrile (NBR)Nitrile / vinyl-nitrile foam Closed-cell NBR foam Condensation + oil resistance ASTM C534; D1056; E96 Cold pipe, mechanical room
    Crosslinked / Expanded PE FoamClosed-cell PE foam Closed-cell polyethylene Economical closed-cell wrap / collar ASTM D1056 / maker TDS; E96 Cold/warm pipe, spacers
    Vapor-Retarder Facings / JacketsLow-perm facing FSK / foil-scrim, low-perm film The vapor boundary on faced systems ASTM C1136; E96 Faced cold duct / pipe
    Duct liner, hot service, and connection gaskets
    Glass-Fibre Duct Liner & PaperFibrous-glass liner / paper Fibrous glass Thermal + acoustic; erosion; 25/50 ASTM C1071; UL 181; E84 Duct liner, hot gasket paper
    Silicone Foam (BISCO® HT/BF)Closed-cell silicone foam Closed-cell silicone Widest temperature + UL 94 V-0 UL 94; ASTM D1056; E84 per TDS Hot duct/plenum gaskets
    Neoprene Foam & SolidClosed-cell / solid neoprene Closed-cell neoprene / solid CR Weather + oil; flange gaskets ASTM D1056 (foam); D2240 (solid) Duct-flange gaskets
    PTFE-Coated FibreglassPTFE-coated glass cloth PTFE-coated fibreglass High-temperature, low-friction facing Maker TDS; E84 where reported Hot joints, slip facings
    Notes. Selection drivers are family-level descriptors; per-grade values live on the maker TDSs with the methods named. NFPA 90A/90B and any installed-system rating do not appear as columns here because they attach to the installed building: the code compliance and the assembly rating belong to the installed system, and the materials support designs evaluated to them. This matrix is a selection aid; the TDS on file governs for the selected grade. Solid EPDM and pressed-felt saddle families are covered in the zones and material reference alongside these eight.
    Found your candidate family? The fastest next step is the drawing: H-O reviews it against these selections and the service conditions and comes back with a manufacturable option and the TDS.
    Already know your spec?

    Skip ahead and request your engineering review now

    If your drawing set already calls out a cold-pipe collar or wrap, a duct-liner die-cut, a vapor-retarder-faced jacket, a duct-flange gasket, or a kitted set of fitting collars and closures, send it over for engineering review against the TDSs, the service conditions, and the standards language.

    What goes wrong in the field

    Duct & pipe insulation failures you can prevent at spec

    Duct and pipe insulation fails quietly first: a cold line that starts to sweat a season later, a wall sized from a generic table, a vapor boundary open at one fitting, a plenum material with no fire class, or a duct liner that sheds into the airstream. Six patterns cover most of what goes wrong, and each is a specification decision made before the first part is cut.

    Field caution

    On cold service, the failure is cumulative and hidden. Vapor drives inward for the building's life, so a breached boundary or a thin wall does not fail on day one; it wets the insulation, collapses the R-value, drips, and corrodes the pipe underneath over months. Size to the design dew point, seal the boundary continuously at the fittings, and cite the standards by designation; never write "code-compliant" on a part, and keep every performance claim traced to the grade TDS.

    Show all 6 failure modes tap to expand

    1. A cold line that sweats because the job was treated as R-value only

    Fix — design the below-dew-point line for vapor drive, not R-value alone: pick a closed-cell elastomeric whose low water-vapor permeance (ASTM E96) is the built-in vapor retarder, size the wall to keep the surface above the design dew point, and seal the boundary continuously.

    The single dominant failure on cold service is condensation: an undersized wall, a higher-conductivity material than assumed, or a breached vapor boundary lets a point on or inside the wall fall below the dew point; vapor driven inward condenses, wets the insulation, collapses its R-value, drips, and corrodes the pipe (corrosion-under-insulation).

    Send the service temperature and the design dew point, and the class and thickness follow. [6]

    2. A wall thickness picked from a generic table instead of the design dew point

    Fix — size the wall from the vendor condensation-control table for the actual design pipe temperature, ambient temperature, and relative humidity, not a one-size table. Being short by as little as ~0.25–0.50 in. can drop the surface below the dew point and start condensation even with a good material, because the thickness is what holds the whole cross-section, and the surface, above the dew-point isotherm.

    State the design conditions on the drawing and let the thickness fall out of the table; the k value that feeds it is only meaningful with its mean temperature (ASTM C177/C518). [14]

    3. A vapor boundary intact everywhere except the fitting that governs

    Fix — make the fitting collars, seams, and terminations die-cut, vapor-tight parts, not field-trimmed gaps. The wrap can be intact along the straight run and still fail if the collar at a valve or elbow and the termination are not sealed vapor-tight: vapor bypasses the good material at the weakest 5% of the surface, reaches the cold metal, and condenses there. On faced systems the facing (ASTM C1136) and its sealed seams carry the boundary.

    Call out the fittings and terminations and let H-O the collars, saddles, and closures so the boundary is continuous where it is weakest. [3]

    4. A material with no 25/50 index used in a duct or plenum location

    Fix — spec for the fire code of the location, not just the thermal duty: confirm any 25/50 requirement and read the flame-spread / smoke-developed index off the grade TDS. A material with no surface-burning evaluation (or the wrong facing) used where NFPA 90A/90B requires flame-spread ≤25 and smoke-developed ≤50 per ASTM E84 puts the location out of code.

    Use a glass-fibre or silicone-foam grade with the 25/50 index the location needs, with a UL 94 V-0 class on any plastic-foam grade; the index is a material class on the TDS, and the compliance belongs to the installed building.

    [7]

    5. A duct liner that erodes and sheds because it was not matched to the air velocity

    Fix — match the duct liner and its edge treatment to the system's service air velocity per UL 181 / ASTM C1071. A liner not rated for the system velocity erodes and sheds fibres into the airstream, and an unfaced edge frays at a cut. A cleanly die-cut, sealed liner edge does not fray, which is exactly where an unfaced field cut starts to erode.

    Send the duct dimensions and the design air velocity, and select the liner and its edge treatment for that velocity; the ASTM C1071 property set (apparent k, sound absorption, erosion, water-vapor sorption, combustion) is on the grade TDS. [2]

    6. The wrong elastomer or facing for the exposure (UV, oil, or wash-down)

    Fix — match the elastomer and facing to the real exposure, not only the thermal duty. A foam or facing that hardens under UV where duct or pipe runs exposed outdoors, or a facing incompatible with a wet mechanical-room or wash-down area, is a material-to-exposure mismatch that shows up as cracking, hardening, or a failed facing. Use EPDM where UV and weather dominate, nitrile where oil resistance drives, silicone foam for the widest temperature range, and a facing rated for the wet or wash-down exposure.

    Name the exposure (indoor / outdoor / wash-down) and any UV or oil contact, and the family and facing follow. [1]

    Reference

    Material reference

    Detailed specs for the insulation and gasket families referenced on this page: the cold-service insulation (closed-cell elastomeric EPDM and nitrile, crosslinked/expanded PE foam, and the low-perm vapor-retarder facings), the duct and hot-service families (glass-fibre duct liner and paper, silicone foam), and the connection-gasket families (neoprene foam and solid, PTFE-coated fibreglass, with solid EPDM and pressed-felt saddles alongside).

    Values are per the maker TDS on file for each grade with the method named; the NFPA 90A location requirement and any system rating are cited by designation only, with the compliance belonging to the installed building.

    H-O die-cuts, kiss-cuts, waterjet-cuts, slits, and kits every family to drawing.

    Read the two columns separately

    Material class (per the maker TDS): thermal conductivity k per ASTM C177/C518, water-vapor permeance per ASTM E96, ASTM E84 surface-burning 25/50 index, ASTM C534/C1071 conformance, ASTM D1056 cellular class, UL 94 V-0. Code compliance & system rating (per the installed building, by designation): NFPA 90A/90B, the condensation-control result, and any assembly rating.

    Rule of thumb: write the material class on the part callout, and cite the code and system requirement by designation with the compliance belonging to the installed building.

    Two labels, two owners. The material carries its class; the installed building carries the code compliance and the condensation-control result.
    Closed-Cell Elastomeric EPDM FoamBelow-dew-point pipe collars & wraps · ASTM C534 · low WV permeance is the built-in vapor retarder
    CompositionFlexible closed-cell EPDM (ethylene propylene diene monomer) foam, sheet and tubular form
    Vapor roleVery low water-vapor permeance is the built-in vapor retarder on cold service, so a correctly sized and sealed wall needs no separate barrier in most indoor runs
    Why EPDMWeather- and UV-tolerant elastomer; the default where duct or pipe runs exposed as well as the general cold-service workhorse
    MethodsASTM C534 (elastomeric cellular spec); C177/C518 (k with mean temperature); E96 (permeance); C411 (max continuous use, ~250 °F on AP-class grades per the maker TDS)
    Form factorsDie-cut collars, wraps, saddles, and hanger inserts; waterjet-cut thick sections; laminated foam-plus-facing stacks
    Where it lives in this application: chilled-water, refrigerant-suction, condensate, and cold domestic-water pipe, plus dual-temperature duct wrap, where condensation control governs. The thickness comes from the vendor condensation-control table for the design pipe temperature, ambient temperature, and relative humidity; the fitting collars and closures are so the vapor boundary is continuous where it is weakest.

    The low permeance is the vapor retarder, so the emphasis is a continuously sealed wall of adequate thickness, not a high-perm blanket plus a separate barrier. The condensation-control result belongs to the installed building; H-O supplies the part and its TDS.

    Closed-Cell Nitrile / PVC-Nitrile Foam (NBR)Economical, oil-resistant cold-line wrap & collar · ASTM C534 / D1056
    CompositionFlexible closed-cell nitrile (NBR) / vinyl-nitrile (PVC-NBR) foam
    Why nitrileCondensation control with oil resistance; the economical closed-cell wrap and collar for refrigeration and mechanical-room cold lines
    Vapor roleLow water-vapor permeance closed-cell structure resists the inward vapor drive; permeance per ASTM E96 on the grade TDS
    MethodsASTM C534 (elastomeric cellular); D1056 (cellular-rubber class); E96 (permeance)
    Form factorsDie-cut collars, wraps, and gaskets; slit tape; laminated stacks
    Where it lives in this application: refrigeration and mechanical-room pipe, indoor cold lines, and connection gaskets where oil resistance or cost drives the choice over EPDM. Sized and sealed like any cold-service part so the surface stays above the design dew point.

    Where UV and weather dominate the exposure, EPDM is the more weather-tolerant choice; nitrile is the oil-resistant, economical indoor option.

    Glass-Fibre Duct Liner & High-Temperature PaperThermal + acoustic duct liner · ASTM C1071 / UL 181 · 25/50 per ASTM E84 on the TDS
    CompositionFibrous-glass duct liner and high-temperature glass-fibre paper (MANNIGLAS®-class grades)
    Why glass-fibreThermal and acoustic duct lining with erosion resistance; inorganic and non-combustible, with a 25/50 surface-burning class on the rated grade
    Duct-liner specASTM C1071 catalogues apparent k, sound-absorption coefficients, erosion, water-vapor sorption, and combustion characteristics for air to 250 °F; erosion / service velocity per UL 181
    MethodsASTM C1071 (fibrous-glass duct liner); UL 181 (erosion); ASTM E84 (25/50 indices, per grade TDS)
    Form factorsDie-cut liner pieces with sealed edges, gasket paper, and barrier layers
    Where it lives in this application: supply and return duct and plenum liner where thermal and sound-absorbing performance both matter, plus high-temperature glass-fibre gasket paper on the hot side. The liner is matched to the system air velocity so it does not erode; the edge is sealed so it does not fray into the airstream.

    The 25/50 index and the ASTM C1071 property set are material-level results on the grade TDS; the NFPA 90A compliance and the finished acoustic performance belong to the installed building.

    Silicone Foam / Sponge (BISCO® HT/BF class)Hot-duct / plenum gaskets · widest temperature range · UL 94 V-0 grades per TDS
    CompositionClosed-cell silicone foam / sponge (BISCO® HT and BF closed-cell series)
    Why siliconeThe widest temperature range of the families here, with UL 94 V-0 grades for flame- and heat-adjacent duty in ducts and plenums
    Fire classUL 94 V-0 available on the rated grade; ASTM E84 surface-burning index where reported on the grade TDS
    MethodsUL 94 (flammability class); ASTM D1056 (cellular class); ASTM E84 per TDS; temperature range per the grade TDS
    Form factorsDie-cut and slit gaskets, connection seals, and closures
    Where it lives in this application: hot-duct and plenum gaskets, high-temperature connection seals, and hot-line insulation where the service temperature exceeds the elastomeric range or a UL 94 flame class is called out. The V-0 class and the E84 index are material classes on the grade TDS.

    Reach for silicone foam where temperature endurance or a flame class drives the joint; the range and the class are per the grade TDS, and the code compliance belongs to the installed building.

    Neoprene Foam & Solid PolychloropreneDuct-flange & connection gaskets · ASTM D1056 (foam) / D2240 (solid) · weather + oil
    CompositionClosed-cell neoprene foam and solid polychloroprene (CR) sheet
    Why neopreneWeather and oil resistance at foam closure forces; the general-duty duct-flange and connection gasket
    ClassASTM D1056 cellular classes on the foam grades; durometer per ASTM D2240 on the solid grades, per the grade TDS
    MethodsASTM D1056 (cellular foam class); D2240 (durometer, solid); D575 (rubber in compression)
    Form factorsDie-cut transverse-flange, slip-and-drive, and access-door gaskets; closure strips
    Where it lives in this application: the sheet-metal duct connections, transverse-flange (companion-flange and slide-on-flange) joints, slip-and-drive connections, access-door and plenum joints, and equipment transitions, where the gasket seals the air leakage that wastes fan energy and, on cold duct, closes the vapor boundary across the joint. Sized to the flange closure force and gap.

    Where a solid strip suits the joint, the solid polychloroprene grade takes over; where UV, ozone, or a wet exposure dominates, the EPDM track is the better default.

    Crosslinked / Expanded Polyethylene (PE) FoamEconomical closed-cell pipe wrap, collars & spacers · ASTM D1056 / maker TDS
    CompositionClosed-cell crosslinked polyethylene (XLPE) and expanded polyethylene (EPE) foam
    Why PE foamEconomical closed-cell wrap, pipe collars, corner pieces, and thermal spacers; closed-cell structure limits moisture uptake
    Vapor roleClosed-cell structure resists moisture uptake on cold and warm lines; permeance per the maker TDS
    MethodsASTM D1056 / maker TDS (cellular class); E96 (permeance where reported)
    Form factorsDie-cut collars, corner and takeoff pieces, sleeves, inserts, and thermal spacers
    Where it lives in this application: economical cold and warm pipe wrap and collars, duct corner and takeoff pieces, penetration sleeves, and thermal spacers, plus the corners, damper collars, and closure strips that a continuous wrap cannot cover by itself.

    The economical closed-cell option for wrap, spacer, and collar duty; where the design calls for a specified permeance or a fire class, the elastomeric and glass-fibre tracks take over.

    Vapor-Retarder Facings & JacketsThe vapor boundary on faced cold-service insulation · ASTM C1136 / E96
    CompositionFSK (foil-scrim-kraft) and low-perm film facings and jackets, laminated to foam or fibrous-glass insulation
    Why a facingOn faced cold-service insulation, the facing and its sealed seams carry the vapor boundary; the facing carries the perm rating
    Facing specASTM C1136 is the standard for flexible, low-permeance vapor retarders for thermal insulation; perm per ASTM E96
    MethodsASTM C1136 (facing / jacket spec); E96 (water-vapor permeance)
    Form factorsLaminated foam-plus-facing and foam-plus-scrim stacks; closure strips; sealing tapes and membranes
    Where it lives in this application: the vapor boundary on faced fibrous-glass duct wrap and pipe jacket, and the closure strips at joints and takeoffs, where the facing (not the bulk insulation) carries the perm rating. On faced cold duct the facing and its seams are the boundary that must be continuous.

    On a closed-cell elastomeric wall the material's own low permeance is the retarder; on a fibrous or faced system the facing (ASTM C1136) and its seams carry the boundary, so seam sealing governs.

    PTFE-Coated Fibreglass & Pressed-Felt SaddlesHot-joint facings & pipe-support thermal breaks · maker TDS / SAE J314
    CompositionPTFE-coated glass cloth / film, and wool/blended SAE pressed felt for support saddles
    Why thesePTFE-coated glass gives a high-temperature, low-friction gasket / facing at hot joints and slip points; pressed felt gives an anti-vibration thermal-break saddle at supports and hangers
    MethodsPTFE-coated glass: maker TDS (temperature range), ASTM E84 where reported. Pressed felt: SAE J314 / maker TDS (density, thickness)
    Where felt fitsThermal-break and anti-vibration saddle at pipe hangers and supports; breaks the metal bridge and damps support noise
    Form factorsDie-cut hot-side facings and slip tapes; felt saddles and hanger thermal-break pads
    Where it lives in this application: PTFE-coated glass at hot-side duct/flange gaskets, release/slip facings, and expansion joints; pressed-felt saddles at pipe hangers and supports where a thermal break and sound damping keep the hanger from short-circuiting the insulation and, on cold lines, from becoming a local sweat point.

    Two component families that finish the job at the hot joints and the metal contacts; per-grade properties govern, on the maker TDS. Fire-stopping at rated penetrations is a separate, tested-assembly discipline (the fire, life safety & smoke-control sibling).

    Engineering questions

    Duct & pipe insulation: engineer-grade FAQ

    Twelve of the questions we hear most from mechanical and insulation contractors, MEP designers, and building owners. If your question isn't here, send a drawing or call, engineering picks up.

    12 questions · click a question to expand its answer

    Why is cold-pipe insulation a condensation problem and not just an R-value problem?

    Because a below-dew-point line drives water vapor inward. When a surface sits below the ambient dew point, moist room air is pushed toward the cold pipe, so the insulation has to do two jobs at once: slow the heat gain (thermal conductivity per ASTM C177/C518) and resist that vapor drive along its whole thickness (water-vapor permeance per ASTM E96), behind a continuously sealed boundary.

    If the wall is too thin, the material more conductive than assumed, or the boundary breached, a point on or inside the wall falls below the dew point and vapor condenses there, wetting the insulation and collapsing its R-value. That is why the controlling numbers on the cold side are the dew point and the permeance, not R-value alone. [6]

    How do I size the wall thickness for a chilled-water or refrigerant line?

    From the vendor condensation-control table for your design conditions, not a generic table. The thickness needed to keep the surface above the dew point depends on the design pipe temperature, the ambient temperature, and the relative humidity, so those three inputs pick the thickness for a given material. Being short by as little as ~0.25–0.50 in. can drop the surface below the dew point and start condensation even with a good closed-cell elastomeric.

    Send the service temperature and the design dew point (or ambient temperature and RH), and H-O confirms the material class and that the specified thickness and a continuous vapor boundary keep the surface above the design dew point; the sizing result belongs to the installed building. [14]

    What is the “built-in vapor retarder” of a closed-cell elastomeric, and do I still need a facing?

    A closed-cell elastomeric foam (EPDM or nitrile) has a very low water-vapor permeance in its own right, so the material is the vapor retarder, and a correctly sized, continuously sealed wall usually needs no separate barrier on indoor runs. The emphasis then shifts to sealing: seams, fitting collars, and terminations must be closed vapor-tight, because the weakest 5% of the surface governs.

    On a fibrous-glass or faced system it is different, the low-perm facing (ASTM C1136) and its sealed seams carry the boundary, and the facing carries the perm rating. So: closed-cell elastomeric, seal the wall; faced fibrous, seal the facing. [3]

    What does 25/50 mean, and where is it required?

    25/50 is a flame-spread index of 25 or less and a smoke-developed index of 50 or less, measured per ASTM E84 (equivalently UL 723), the Steiner Tunnel test. It is the common building requirement for materials installed in ducts and plenums, set by NFPA 90A (and NFPA 90B for warm-air heating), and it corresponds to Class A / Class 1.

    The index belongs to the tested material grade and is reported on the maker TDS; the requirement attaches to the location, and the code compliance belongs to the installed building. Confirm any 25/50 requirement for your duct or plenum location and read the index off the grade TDS. [7]

    ASTM C177 vs. C518: which thermal-conductivity method should the TDS cite?

    Both are steady-state methods that report k and R at a stated mean temperature; the difference is the apparatus and the use. ASTM C177 is the guarded-hot-plate method, the reference/precision technique used for design data. ASTM C518 is the heat-flow-meter method, faster and used for production QA and routine comparison. Because k rises with temperature, a k value only means something with its mean temperature, so cite the method and the mean temperature together.

    For a spec, either method is acceptable as long as the value is reported at the mean temperature that matches your service. [4]

    How is water-vapor permeance measured, and what is a perm?

    Water-vapor transmission is measured per ASTM E96, by the desiccant (dry-cup) or water (wet-cup) method, and reported in perms (grain per hour per square foot per inch of mercury), or, for a material, in perm-inch (permeability). On cold service the low permeance of a closed-cell elastomeric is the vapor retarder; on a faced product the facing carries the perm rating. Cite the method (dry vs wet cup) and the perm value from the grade TDS, because the two cup methods can give different numbers. Lower perm means a tighter vapor boundary. [6]

    EPDM or nitrile for a cold line, and when does silicone come in?

    Both EPDM and nitrile are closed-cell elastomerics whose low permeance is the vapor retarder; the split is exposure and cost. EPDM is the weather- and UV-tolerant default, the better choice where the line runs exposed outdoors. Nitrile (NBR / PVC-NBR) is the oil-resistant, economical option for indoor and mechanical-room cold lines. Silicone foam is not primarily a cold-service material: it comes in on the hot side and in plenums, where the widest temperature range and UL 94 V-0 grades matter, or where a hot connection gasket needs a flame class.

    Match the family to the service temperature and the exposure, and confirm the class on the grade TDS. [1]

    What governs a duct liner selection, thermal or acoustic?

    Both, plus the air velocity. A fibrous-glass duct liner does two jobs, cutting conductive heat gain or loss through the sheet metal and absorbing fan and airflow noise, and ASTM C1071 catalogues what it must deliver: apparent thermal conductivity, sound-absorption coefficients, erosion resistance, water-vapor sorption, and combustion characteristics, for air to 250 °F. The third input is the system's air velocity, because the liner surface must withstand it without eroding or shedding fibres, verified per UL 181.

    Where a wipeable, non-fibrous surface is required (labs, healthcare, wash-down), a closed-cell foam liner is the alternative. Send the duct dimensions and the design air velocity, and the liner and its edge treatment follow. [2]

    Are these parts “code-compliant” or “fire-rated”?

    No part is, and no honest supplier will claim otherwise or call one "fireproof". What the materials carry is their own documentation: material-level classes such as a thermal conductivity (k per ASTM C177/C518), a water-vapor permeance (per ASTM E96), a 25/50 surface-burning index (per ASTM E84), an ASTM C534 / C1071 conformance, and a UL 94 class, all on the grade TDS, plus lot-code traceability.

    The code compliance (NFPA 90A), the system rating, and the finished condensation-control result belong to the installed building, cited by designation. H-O supplies the converted part and the paperwork; the installed system carries the compliance. [10]

    What is corrosion-under-insulation, and how does the spec prevent it?

    Corrosion-under-insulation is the corrosion of the pipe surface that happens when condensate is trapped against cold metal under a breached or undersized insulation system. On a below-dew-point line with a broken vapor boundary, vapor driven inward reaches the cold pipe and condenses; the trapped moisture wets the insulation, drips, and corrodes the pipe over months and years, out of sight.

    The spec prevents it the same way it prevents sweating: size the wall to the design dew point, choose a low-permeance closed-cell material, and seal the vapor boundary continuously at every seam, collar, and termination so vapor never reaches the cold metal. That continuity at the fittings is why the collars and closures are parts, not field offcuts. [1]

    Can H-O kit a whole run of fitting collars, wraps, and closures?

    Yes: die-cut collars, wraps, saddle pieces, liner pieces, gaskets, and closure strips can ship as kitted sets, sized to a run of fittings, parts on liner in install order, with lot-code TDS records per material. Kitting the fitting parts is exactly how the vapor boundary stays continuous at the weakest 5% of the surface, because the collars at valves and elbows and the closures at terminations arrive as parts instead of field-trimmed gaps.

    H-O die-cuts, kiss-cuts, waterjet-cuts (thick sections), slits, and laminates (foam-plus-facing or foam-plus-scrim stacks) to drawing. [3]

    Does H-O mold or extrude these materials, or convert them?

    H-O and converts sheet, roll, and tubular stock to drawing; molding and extrusion are not in-house services, and extruded profiles are coordinated through a partner network (made-to-order, 4–6 week tooling). Conversion runs in Winsted, Connecticut under an ISO 9001:2015 certified quality management system with material traceability and lot-code TDS records. What ships is custom, made to order to your pipe run, duct size, or connection detail.

    H-O is a die-cutter and converter, not a stocking distributor of finished insulation, with multiple working material relationships across the elastomeric, glass-fibre, silicone, and PE families. [13]

    Definitions

    Glossary: terms used on this page

    Quick reference for the thermal, vapor, and fire terminology used throughout. Each entry links to the relevant standard or test method where applicable. Every performance term is defined so the material class stays with the grade and the code compliance stays with the installed building.

    Dew point

    The surface temperature at which ambient moist air begins to condense. The cold-service design target is to keep the whole insulation cross-section, and its outer surface, above the design dew point; thickness is selected from the vendor condensation-control table for the design pipe temperature, ambient temperature, and relative humidity.

    Vapor drive (inward, cold service)

    The direction moisture is pushed by a vapor-pressure difference. On a below-dew-point line the drive is inward, from the warm humid room toward the cold pipe, the opposite of a hot line, which is why the vapor boundary must be continuous and the wall thick enough to hold the surface above the dew point.

    Water-vapor permeance / perm (ASTM E96)

    The rate at which water vapor passes through a material, measured per ASTM E96 [6] by the desiccant (dry-cup) or water (wet-cup) method and reported in perms (or perm-inch for a material). On cold service the low permeance of a closed-cell elastomeric is the vapor retarder; on a faced product the facing carries the perm rating.

    Vapor retarder / vapor boundary

    The low-permeance layer that resists the inward vapor drive on cold service. In a closed-cell elastomeric it is the material itself; on a faced system it is the low-perm facing (ASTM C1136 [3]) and its sealed seams. It must be continuous, because vapor bypasses it at the weakest 5% of the surface, the seams, collars, and terminations.

    Thermal conductivity (k) & R-value (C177 / C518)

    k is the material's conductive heat-transfer rate (BTU·in/hr·ft²·°F or W/m·K); R = thickness / k. Measured per ASTM C177 [4] (guarded hot plate, reference/precision) or ASTM C518 [5] (heat flow meter, production QA). Both are steady-state and report k and R at a stated mean temperature; k rises with temperature, so cite the method and the mean temperature.

    25/50 flame-spread / smoke-developed (ASTM E84 / UL 723)

    A flame-spread index of 25 or less and a smoke-developed index of 50 or less per ASTM E84 [7] (equivalently UL 723 [8]), the common requirement (Class A / Class 1) that NFPA 90A/90B set for materials in ducts and plenums. The index is a material class on the grade TDS; the compliance belongs to the installed building.

    Duct-liner service velocity / erosion (UL 181)

    The airstream velocity the liner surface must withstand without eroding or releasing fibres, verified per UL 181 [9] erosion and catalogued in the fibrous-glass duct-liner spec ASTM C1071 [2]. A liner rated below the service velocity erodes and sheds; a cleanly die-cut, sealed edge does not fray.

    Closed-cell elastomeric (ASTM C534)

    Flexible closed-cell elastomeric cellular insulation (EPDM or nitrile) in sheet and tubular form, specified by ASTM C534 [1] (thermal conductivity, water absorption, water-vapor permeability, shrinkage, corrosion). Its own low permeance is the built-in vapor retarder, so a sized and sealed wall needs no separate barrier on most indoor cold-service runs.

    Corrosion-under-insulation (CUI)

    Corrosion of the pipe surface caused by condensate trapped against cold metal under a breached or undersized insulation system. On a below-dew-point line with a broken vapor boundary, inward-driven vapor condenses on the cold pipe, wetting the insulation and corroding the pipe over time. The spec prevents it by sizing to the dew point and sealing the boundary continuously.

    Hot-surface performance (ASTM C411)

    The hot-surface performance test for high-temperature thermal insulation, per ASTM C411 [11], the context for a material's maximum continuous-use temperature (for example, closed-cell elastomeric to about 250 °F per the maker TDS, per the AP/ArmaFlex data [15]). Values are per the grade TDS.

    Low-permeance facing / jacket (ASTM C1136)

    A flexible, low-permeance vapor retarder for thermal insulation, specified by ASTM C1136 [3]. On faced cold-service insulation the facing (FSK / foil-scrim-kraft or low-perm film) and its sealed seams are the vapor boundary, and the facing carries the perm rating (per ASTM E96 [6]).

    Compliance belongs to the installed building

    The honesty rule for this page: the material classes (k, permeance, the 25/50 index, ASTM C534/C1071 conformance, UL 94) attach to the tested grade per its TDS, while the code compliance (NFPA 90A [10]), the assembly rating, and the finished condensation-control result belong to the installed building. A converted part carries its own material classes and supports a compliant installation without being "code-compliant" or "fireproof" itself.

    Last updated · Reviewed by H-O Products engineering (ISO 9001:2015 certified converter, Winsted, CT).

    Citations

    Standards, test methods & technical references

    The standards, test methods, and maker technical data sheets cited throughout this page. Installation and code standards are cited by designation: they govern the installed building, and the code compliance and system rating belong to the installed / tested system. Standards editions current as of July 2026; verify against the publishing body before final spec. H-O converts materials aligned to the material-level methods on the source maker's TDS; H-O does not certify installations or independently certify materials unless explicitly stated on the quote.

    [1] ASTM C534 / C534M (material-level)

    Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form. The material spec for closed-cell elastomeric pipe/sheet insulation (thermal conductivity, water absorption, water-vapor permeability, shrinkage, corrosion). Reported on the grade TDS. astm.org (C534)

    [2] ASTM C1071 (material-level)

    Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound-Absorbing). Requires apparent thermal conductivity, sound-absorption coefficients, erosion resistance, water-vapor sorption, and combustion characteristics for air to 250 °F. Reported on the grade TDS. astm.org (C1071)

    [3] ASTM C1136 (material-level)

    Standard Specification for Flexible, Low-Permeance Vapor Retarders for Thermal Insulation. The facing / jacket spec for faced duct and pipe insulation on cold service; the facing and its seams carry the vapor boundary and the perm rating. astm.org (C1136)

    [4] ASTM C177 (material-level)

    Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus. The reference/precision method for thermal conductivity (k) and R; reports at a stated mean temperature. astm.org (C177)

    [5] ASTM C518 (material-level)

    Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus. The faster production-QA method for thermal conductivity (k) and R; reports at a stated mean temperature. intertek.com (C518)

    [6] ASTM E96 / E96M (material-level)

    Standard Test Methods for Water Vapor Transmission of Materials (desiccant / dry-cup and water / wet-cup methods). Reports permeance in perms (or perm-inch for a material); the vapor-retarder metric on cold-service insulation and facings. astm.org (E96)

    [7] ASTM E84 (material-level)

    Standard Test Method for Surface Burning Characteristics of Building Materials (Steiner Tunnel). Flame-spread index (FSI) and smoke-developed index (SDI); the 25/50 requirement (FSI ≤25, SDI ≤50) is Class A / Class 1. A material-level result on the maker TDS. astm.org (E84)

    [8] UL 723 (material-level)

    Standard for Test for Surface Burning Characteristics of Building Materials, the companion to ASTM E84 (same Steiner Tunnel method, flame-spread and smoke-developed indices). Cited by designation; the index is a material class on the grade TDS. shopulstandards.com (UL 723)

    [9] UL 181 (by designation)

    Standard for Factory-Made Air Ducts and Air Connectors, the context for duct-liner erosion and service-velocity requirements. Cited by designation; the erosion / service-velocity behavior is verified on the liner grade. shopulstandards.com (UL 181)

    [10] NFPA 90A / 90B (by designation)

    Standard for the Installation of Air-Conditioning and Ventilating Systems (90A) and Warm Air Heating and Air-Conditioning Systems (90B): the source of the 25/50 requirement for materials in ducts and plenums. Cited by designation; the code compliance belongs to the installed building. nfpa.org (NFPA 90A)

    [11] ASTM C411 (material-level)

    Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation. The context for maximum continuous-use temperature (for example, closed-cell elastomeric to about 250 °F per the maker TDS). Reported on the grade TDS. astm.org (C411)

    [12] UL 94 (material-level)

    Standard for Tests for Flammability of Plastic Materials for Parts in Devices and Appliances (HB, V-0, V-1, V-2 classes). A material-level flammability class carried on the maker TDS (for example, V-0 on the rated silicone-foam grades). shopulstandards.com (UL 94)

    [13] ASTM D1056 / D2240 / D575 (material-level)

    ASTM D1056 (Flexible Cellular Materials, Sponge or Expanded Rubber, the cellular-rubber classification), D2240 (Rubber Property, Durometer Hardness), and D575 (Rubber Properties in Compression), the gasket-foam and solid-rubber classes for the neoprene, nitrile, and EPDM families. Reported on the grade TDS. astm.org (D1056)

    [14] Aeroflex USA / Engineered Materials — elastomeric (EPDM) pipe insulation & ASTM C534 guidance

    Closed-cell elastomeric (EPDM) pipe-insulation technical guidance, including the “ASTM C534 breakdown” and the dew-point / thickness relationship (undersizing thickness by ~0.25–0.50 in. can drop the surface below the dew point). Manufacturer technical reference; values per the maker TDS. aeroflexusa.com (elastomeric pipe insulation)

    [15] Armacell — AP/ArmaFlex closed-cell elastomeric (EPDM) technical specs

    AP/ArmaFlex closed-cell elastomeric pipe/sheet insulation technical data (thermal conductivity, water-vapor transmission on the order of 0.08 perm-inch, and ASTM C411 hot-surface performance to about 250 °F). Manufacturer technical data sheet; values per the maker TDS. armacell.com (AP/ArmaFlex)

    [16] SAE J314 / NAIMA duct-liner reference (material-level)

    SAE J314 (wool-felt and blended pressed-felt grades) for the pipe-support saddle and hanger thermal-break pads, alongside the NAIMA / Insulation Institute fibrous-glass duct-liner reference (design, fabrication, installation, UL 181 erosion, ASTM C1071). Values per the maker TDS. insulationinstitute.org (fibrous-glass duct liner)

    Updated . Standards editions and links current at publication; verify against the publishing body before final spec. Standards cited by designation (NFPA 90A/90B, UL 181) govern the installed building; H-O converts materials aligned to the material-level methods via the maker TDS and does not certify installations or independently certify materials unless explicitly stated on the quote. Lot-specific documentation available on request. No maker named in this block is a competitor of H-O.

    What to send H-O

    To review your duct or pipe insulation part, send:

    • Line or duct type and service temperature (cold / hot)
    • The design dew point (or ambient temperature + relative humidity) on cold service
    • Pipe OD or duct dimensions
    • Required fire class (25/50?) for the location
    • Facing / vapor-retarder requirement
    • Connection or flange detail for gaskets
    • Design air velocity for duct liner
    • Exposure (indoor / outdoor / wash-down)
    • Adhesive / liner / lamination requirements
    • Prototype and annual volume
    Quote request

    Get a duct & pipe insulation engineering quote

    Send a pipe run, duct size, or connection detail with the service conditions. We typically respond within one business day with a material recommendation, prototype lead time, and TDS verification against your service temperature, design dew point, fire class, and the standards language, framed correctly so the code compliance stays with the installed building.

    Contact
    Company address
    Your application
    Part & quantity
    Typical response in one business day. Samples typically 3–5 business days; production in about 2 weeks. MOQ varies by material and part. Expedited service available.

    Material data & standards. All thermal-conductivity (k), water-vapor permeance, surface-burning, hot-surface, and flammability values on this page are taken from the source maker's technical data sheets with the method named (ASTM C534, C1071, C1136, C177, C518, E96, E84, C411; UL 94 classes per the listed grade TDSs).

    Installation and code standards (NFPA 90A/90B, UL 181, UL 723) are cited by designation only: they govern the installed building, the 25/50 fire class attaches to the location, the code compliance and the condensation-control result belong to the installed system, and the materials on this page support designs evaluated to them.

    H-O converts materials; H-O does not install insulation systems, does not certify or list installations or assemblies, and does not independently certify materials against the standards unless explicitly stated on the quote. Aerogel insulation is outside the scope of this building duct-and-pipe page; the relevant families here are the closed-cell elastomeric, glass-fibre, silicone, and PE materials above. Verify against the maker TDS and the vendor condensation-control tables.

    Conversion scope. H-O and converts sheet, roll, and tubular stock to drawing in Winsted, Connecticut: die-cut and kiss-cut collars, wraps, saddles, liner pieces, gaskets, and closures, slit tape, waterjet-cut thick sections, laminations, and kitted collar-and-closure sets, with material traceability and lot-code TDS records.

    H-O is a die-cutter and converter, not a molder, an extruder, or a stocking distributor of finished insulation; molded and extruded profiles are coordinated through a partner network (made-to-order, 4–6 week tooling). Lead-time and MOQ details are in the process strip and the quote form above.

    Get Quote →