Custom Busbar, Transformer & Power Distribution Insulation
H-O Products die-cuts and converts aramid paper, polyimide film, mica barrier sheet, glass-epoxy and composite laminate, and fish paper into the busbar barriers, phase supports, transformer layer insulation, and slot liners inside distribution transformers, medium- and low-voltage switchgear, and substation gear, built to your drawing.
Built for: feeder and bus-duct barriers and wrap in MV/LV distribution boards, padmount- and substation-transformer coil and layer insulation, collector-bus barriers in wind and solar plants and BESS-adjacent power blocks, rigid standoffs that hold live conductors apart in switchyards, and the slot, washer, and end-lamination parts that carry the thermal class (up to Class R 220 °C) and the creepage the equipment standard demands.
To insulate power-distribution equipment, select on three axes. Thermal class (IEC 60085 / IEEE C57): match the class letter (A 105 through R 220 °C) to the winding hotspot — Nomex® aramid paper is the 220 °C backbone for transformer layer and coil insulation.
Dielectric strength (ASTM D149 / IEC 60243 per TDS): Kapton® polyimide film where the barrier bends and wraps busbars; fish paper / vulcanized fibre (roughly 6–10 kV/mm) for LV slot liners; Durostone® composite (16 kV/mm per TDS) where the barrier also carries load. Creepage/clearance per IEC 60664-1 / IEC 62271: the surface path governs under pollution, set by pollution degree and material group (CTI per IEC 60112).
The remaining duties are mapped in the When-to-spec list. Values are per the TDS on file; see the material reference below for ordering details.
Material- and system-level, by designation: IEC 60085 (thermal classes / designation) · IEC 60664-1 (LV insulation coordination: creepage, clearance, pollution degree, material group) · ASTM D149 / IEC 60243 (dielectric breakdown / electric strength) · IEC 60112 (comparative tracking index, CTI) · NEMA LI 1 (industrial laminate grades G-10 / FR-4 / G-11) · UL 1446 (systems of insulating materials) · UL 94 (flammability classes) · UL 746B (long-term polymeric evaluation, RTI) · and the switchgear-assembly family (IEC 62271 for MV, IEC 61439 for LV, IEEE C37.20.2 for metal-clad).
Editions current as of July 2026; verify before final spec.
- Transformer layer / coil insulation: Nomex® 410 / 411
- Busbar wrap / thin barrier: Kapton® polyimide film
- Load-bearing phase barrier / standoff: G10/FR4 / Durostone®
- High-temperature / arc-adjacent barrier: mica sheet / ManniGlas®
- LV slot liner / washer / end lamination: fish paper / vulcanized fibre
- Demanding thin-film position: PEEK film (APTIV®)
- Thermal barrier by hot equipment: ArmaGel® aerogel
This guide is for utility spec engineers, EPC contractors, and generation and switchgear OEMs specifying insulation for substation and switchyard gear, padmount and distribution transformers, feeder and bus-duct runs, and the collector buses that gather wind, solar, and BESS output before it reaches the grid: busbar barriers and wrap, transformer layer and coil insulation, phase-barrier standoffs, and slot/washer parts for MV and LV distribution equipment.
If you build the machine, drive, or switchgear cabinet rather than distribute or collect the power, the busbar, transformer & motor insulation sibling page is the OEM edition of this same catalog.
Where are you in the spec process?
This page serves engineers who already know the grade they want and engineers still working out which insulation class, dielectric margin, and creepage the equipment demands. Pick the path that matches where you are; you don't have to read the rest.
Send a drawing, get a quote
A Nomex® layer-insulation build, a Kapton® busbar wrap, a mica or ManniGlas® barrier, a G10/FR4 or Durostone® standoff set, or fish-paper slot liners on your drawing.
Skip to the quote form →Build the spec axis by axis
Six selection factors (thermal class, dielectric margin, creepage/clearance, mechanical load, environment, and system qualification), an insulation-material selector, and nine families with TDS-cited methods and by-designation standards language.
Start with selection factors →
-
1Send drawingUpload a DXF, STEP, or PDF, or describe the busbar layout, coil, or cubicle. A sample part works too.
-
2Material reviewEngineering reviews the thermal class, dielectric margin, and creepage/clearance against the maker TDSs, and frames the standards language correctly: material classes and dielectric strength by TDS; thermal class per IEC 60085; creepage per the equipment standard; system qualification (UL 1446) with the tested winding.
-
3PrototypeTypically 3–5 business days for common configurations on materials we keep on hand. Standard production 2 weeks; special orders run custom lead times. Made-to-order; MOQ varies by material and part.
-
4ProductionStandard production runs ship about 2 weeks after drawing approval, on flatbed die-cutting, slitting for wrap and roll stock, and kitting for coil-insulation sets. Ongoing parts run with material traceability and lot-code TDS records.
Voltage class & hotspot → material selection → converted barrier / layer → production supply.
- 1Voltage class & hotspotRated voltage, impulse withstand (Uimp), and the winding hotspot / thermal class the part must carry.
- 2Set the three axesThermal class (IEC 60085), dielectric margin (ASTM D149 / IEC 60243), and creepage/clearance (IEC 60664-1 or IEC 62271) for the pollution degree.
- 3Choose material familyPaper where it wraps, film where it bends, laminate where it bears load, inorganic sheet where temperature or arc drives it.
- 4Add adhesive / liner / laminationPSA backing, release liner, or multi-layer lamination applied in-house per the drawing.
- 5Die-cut to drawingClean, sealed edges instead of field-trimmed ones: the edge quality that removes the trim damage that starts most barrier failures.
- 6Quote prototype or productionTDS on file and lot-code traceability for the system file, prototype through full production.
Which distribution-insulation problem are you solving?
Application Zones
Six insulation problems define distribution equipment: the busbar barriers and wrap that hold phase-to-phase and phase-to-ground distance in MV/LV boards; the phase-barrier standoffs that physically support live conductors under fault forces; the distribution-transformer coil and layer insulation that carries the thermal class; the medium-voltage switchgear compartment where creepage and pollution degree govern; the low-voltage slot, washer, and end-lamination parts; and the thermal barriers that live beside hot distribution equipment.
Click a tab to see the stack, the controlling property, and the families H-O converts for that zone.
Busbar barriers & wrap: holding the distance under pollution
A distribution busbar's insulation has one job the voltage makes deceptively simple and the environment makes hard: hold the required distance phase-to-phase and phase-to-ground. Two distances matter, and they are not the same. Clearance is the shortest straight-line gap through air; creepage is the shortest path across the surface of the insulator, and under pollution the surface path is what flashes over.
Kapton® polyimide film wraps the bar where the barrier has to bend and follow the conductor; barrier sheet of glass-epoxy laminate or composite (with a rib that lengthens the surface path) stands between phases where the design needs a rigid wall. The creepage and clearance a board must hold come from the equipment standard's tables (IEC 60664-1 for LV, IEC 62271 for MV), driven by the rated impulse voltage, the pollution degree, and the material group (CTI per IEC 60112).
Die-cutting matters here: a barrier earns its keep only if its edges are clean and its rib is where the drawing put it.
Kapton® Polyimide Film (busbar wrap)The thin dielectric that bends and wraps the bar; dielectric strength per ASTM D149 on the maker TDS, slit and to the busbar geometry. [5]
G10/FR4 Barrier Sheet (NEMA LI 1)Rigid phase barrier with a rib to lengthen creepage; NEMA LI 1 grade designations, cut to the board layout. [6]
Durostone® Composite (high-CTI barrier)Where the pollution degree needs a high material group: EPC 203 reports 16 kV/mm per the TDS (IEC 60243), with CTI per IEC 60112. [4]
Fish Paper / Vulcanized Fibre (LV wrap)Economical LV barrier and wrap, roughly 6–10 kV/mm (NEMA F/FR grades), without fraying at the edges. [11]
Phase barriers & standoffs: the insulation that also carries load
Some distribution insulation does more than block current: it holds the conductor in place against gravity, torque, and short-circuit forces. Standoffs, spacers, and structural phase barriers are the load-bearing members of the insulation system, and the material choice is a mechanical one first. Glass-epoxy laminate (G10/FR4, the NEMA LI 1 grades) machines and into supports and barriers with the strength to survive fault forces and bolt loads.
Where the pollution degree or the arc environment pushes harder, Durostone® composite laminate steps up the tracking resistance and electric strength (EPC 203: 16 kV/mm per TDS). These parts live inside listed assemblies (IEC 61439 for LV, IEC 62271 and IEEE C37.20.2 for MV metal-clad gear), so the barrier's material and geometry are constrained by the assembly's verification, not chosen in isolation.
Send the fault current and the bolt pattern with the drawing; the support gets sized to the load it actually carries, not the voltage alone.
G10/FR4 Glass-Epoxy (NEMA LI 1)Load-bearing standoffs, spacers, and phase barriers; NEMA LI 1 grade designations, machined and to drawing. [6]
Durostone® Composite LaminateHigh-CTI, high-strength barriers and supports for MV gear; EPC 203 reports 16 kV/mm per TDS (IEC 60243), UL 94 listings on rated grades. [9]
Mica Barrier Sheet (arc-adjacent)Inorganic barrier where an arc or high temperature would degrade an organic laminate; family holds roughly 700–800 °C continuous per supplier data. [10]
Distribution-transformer coil & layer insulation: carrying the thermal class
Inside a distribution transformer the insulation problem is thermal endurance across decades. Interlayer and conductor-wrap paper separates turns and layers, and its material is chosen by the thermal class: aramid paper (Nomex® 410 calendered, 411 uncalendered) is the backbone of 220 °C (Class R) designs and the standard for dry-type distribution transformers, while thermally-upgraded kraft and pressboard serve the liquid-immersed side under IEEE C57.154 up to a 180 °C class.
Layer insulation is specified by dielectric strength per ASTM D149 and by the class letter that sets the continuous hotspot; life halves roughly every 10 °C above class, so the class match is the whole game. One sentence governs the paperwork: the insulation SYSTEM (paper/film/varnish combination) is qualified per UL 1446, and the class belongs to the qualified system, not to any single layer.
H-O and slits the layer and lead insulation to the winding drawing; the winding house owns the system qualification.
Nomex® 410 / 411 Aramid PaperLayer, conductor-wrap, and lead insulation; the 220 °C (Class R) backbone, calendered (410) and uncalendered (411) per the maker TDS. [1]
Kapton® Polyimide FilmThin high-dielectric barrier for turn and lead insulation where gauge is tight; dielectric strength per ASTM D149 on the TDS. [5]
Mica Barrier SheetHigh-temperature turn and barrier insulation for the hottest positions; inorganic, dimensionally stable at flame temperatures. [10]
ManniGlas® Glass-Fiber PaperHigh-temperature barrier and backing paper; inorganic glass-fiber sheet with UL 94 listings per the maker TDS. [7]
MV switchgear insulation: creepage and pollution degree govern
In a medium-voltage cubicle the voltage is high enough that the surface path, not the air gap, is usually the limiting distance, and the material group (CTI per IEC 60112) directly sets how much creepage the standard demands.
The insulation here is a mix of thin barrier and load-bearing support: Durostone® composite and G10/FR4 make the compartment barriers and support insulators that hold the bus in metal-clad gear (IEC 62271, IEEE C37.20.2), while mica and ManniGlas® handle the positions where arc exposure or temperature turns the answer inorganic.
The compartment's creepage and clearance are verified in the assembly against the equipment standard; the material's job is to bring a high enough CTI and dielectric strength that the required distances stay manageable in a compact cubicle. Higher rated impulse voltage, heavier pollution, and lower CTI all demand more distance, so the material choice and the geometry trade against each other.
Durostone® Composite (support insulators)Compartment barriers and support insulators for metal-clad MV gear; high CTI and 16 kV/mm (EPC 203) per TDS. [3]
G10/FR4 Glass-EpoxyBarrier partitions and standoffs inside the cubicle; NEMA LI 1 grades machined and die-cut. [6]
Mica Barrier SheetArc-adjacent barriers at the contact and interrupter positions; inorganic surface that does not track or carbonize. [10]
Slot, washer & end lamination: the LV workhorse parts
The low-voltage side of distribution apparatus runs on parts that are ordinary in form and precise in fit: slot liners, insulating washers, end laminations, and small barriers. Fish paper and vulcanized fibre (ZnCl2-treated cellulose, NEMA F/FR grades) are the classic material here, with dielectric strength around 6–10 kV/mm (roughly 150–250 V/mil depending on gauge) and enough tensile strength to be into complex geometries without fraying or delaminating at the edges.
Where the position needs a thinner or more thermally durable film, Kapton® polyimide and PEEK film (APTIV®, with RTI per UL 746B) take over. The whole value of these parts is edge quality and fit: a liner that covers the slot and survives insertion, cut from the drawing rather than trimmed on the bench.
Fish Paper / Vulcanized Fibre (NEMA F/FR)Slot liners, insulating washers, and end laminations; roughly 6–10 kV/mm, clean edges without fraying. [11]
Kapton® Polyimide FilmThin, high-dielectric film for tight barrier and washer positions; dielectric strength per ASTM D149 on the TDS. [5]
PEEK Film (APTIV®)Demanding thin-film positions where long-term thermal ageing matters; RTI per UL 746B, dielectric per ASTM D149 on the TDS. [8]
G10/FR4 (small barriers & washers)Rigid washers, spacers, and small barriers where the part carries a mechanical load; NEMA LI 1 grades. [6]Thermal-adjacent barriers: keeping heat off the neighbors
Not every insulation problem in distribution gear is electrical. Where a transformer, reactor, or resistor runs hot next to temperature-sensitive equipment or an enclosure wall, a thermal barrier buys the most temperature drop per millimeter. ArmaGel® aerogel blanket (our blanket-format aerogel line) is the flexible high-resistance barrier for these positions, with thermal conductivity reported per ASTM C177 on its TDS. Where the same duty has to fit in a few mils, Blueshift AeroZero® polyimide-aerogel film carries the thin-film tier — see the material reference below.
Mica and ManniGlas® glass-fiber paper double as thermal barriers where the surface also has to be inorganic and dimensionally stable at high temperature. These are and converted to the panel or wrap geometry like any other layer; the selection is a heat-flux and gap-budget decision, not a dielectric one.
ArmaGel® Aerogel BlanketFlexible high-resistance thermal barrier near hot distribution equipment; thermal conductivity per ASTM C177 on the TDS. [10]
ManniGlas® Glass-Fiber PaperInorganic high-temperature barrier and backing paper; UL 94 listings per the maker TDS. [7]
Mica Barrier SheetInorganic thermal-and-dielectric barrier at the hottest positions; holds roughly 700–800 °C continuous per supplier data. [10]Six decisions that drive your distribution-insulation spec
A distribution-insulation part is a single-purpose layer with one or two controlling properties. Miss one and the failure is rarely immediate: a class runs hot and embrittles, a surface tracks under pollution, a support cracks under fault, or a system qualification stalls on a layer nobody can document.
Layers carry classes and dielectric strength; systems carry qualifications. A thermal class (IEC 60085) and a dielectric strength (ASTM D149) belong to a material grade per its TDS. The insulation SYSTEM qualification (UL 1446) belongs to the tested paper/film/varnish combination inside the transformer or machine.
Write material classes and dielectric strength on the part callouts, cite the system framework by designation, and never let a drawing imply that a layer is "UL 1446 qualified" on its own: the layer supports a qualified system.
The IEC 60085 / IEEE C57 class letters set the continuous hotspot ceiling: A 105, B 130, F 155, H 180, N 200, R 220 °C. Aramid paper is the 220 °C backbone; match the class letter to the winding hotspot, because insulation life halves roughly every 10 °C above class.
Read the six factors below in order. The first three set the electrical spec (thermal class, dielectric margin, creepage/clearance); the next two add mechanics and environment; the last one closes the paperwork. Every factor names its test method, because in this application the documentation is part of the part.
Show all 6 selection factors tap to expand
Thermal class: match the letter to the hotspot, not to habit
The insulation class is the continuous hotspot ceiling, and it decides the paper before anything else does. The IEC 60085 / IEEE C57 letters run A 105, B 130, F 155, H 180, N 200, R 220 °C; aramid paper (Nomex®) is the 220 °C backbone, thermally-upgraded kraft serves the liquid-immersed side to a 180 °C class under IEEE C57.154, and mica or glass-fiber paper carries the positions above that.
Life halves roughly every 10 °C over class, so an under-classed paper is a design that quietly ages out. Put the winding hotspot and the target class letter on the drawing; the paper family falls out of that number. [1]
Dielectric margin: strength per gauge, read at the fold
Dielectric strength (kV/mm, per ASTM D149 or IEC 60243 on the TDS) sets the puncture margin, but the number on the datasheet is measured on flat, clean material. Real barriers fail at folds, edges, and thin spots, so the working margin sits below the flat-sheet figure.
The split is by mechanics: thin film where the barrier bends (Kapton®, high kV/mm in thin gauge), fish paper or aramid where a conformable sheet suits the position (roughly 6–10 kV/mm for fibre), and composite where the barrier also carries load (Durostone® EPC 203: 16 kV/mm per TDS).
Specify the gauge and the dielectric strength by grade, and add margin for folds and edges. [5]
Creepage & clearance: the surface path governs under pollution
Clearance is the shortest gap through air; creepage is the shortest path across the insulator surface, and under pollution the surface path is what flashes over. The distances come from the equipment standard's tables (IEC 60664-1 for LV, IEC 62271 for MV), driven by the rated impulse voltage, the pollution degree (industrial is typically PD3), and the material group set by the comparative tracking index (CTI, per IEC 60112).
A high-CTI surface (Durostone®) needs less creepage than a low-CTI one for the same voltage, and a rib on a barrier lengthens the surface path without widening the part. State the voltage class, Uimp, and pollution degree; the required creepage and clearance follow. [2]
Mechanical load: film insulates, laminate bears
A phase barrier or standoff that also holds the conductor is a structural member, and thin film cannot do that job. Where the insulation carries gravity, torque, or short-circuit force, the answer is load-bearing laminate: G10/FR4 glass-epoxy (NEMA LI 1 grades) for most supports, Durostone® composite where higher tracking resistance and strength are needed. These parts sit inside listed assemblies (IEC 61439, IEC 62271, IEEE C37.20.2), so the barrier's material and geometry are constrained by the assembly's verification.
Send the fault current and the bolt pattern with the drawing; the support gets sized to the mechanical load, not the voltage alone. [6]
Environment: temperature, arc, oil, and pollution pick the chemistry
The distribution environment filters the material family before performance does. Temperature and arc exposure push the answer inorganic (mica sheet, ManniGlas® glass-fiber paper) where an organic laminate would carbonize or track. Oil-immersed distribution transformers need materials compatible with mineral or ester fluid, and thermally-upgraded kraft and pressboard serve that side.
Heavy pollution raises the creepage demand and rewards a high-CTI surface. Name the temperature, any arc exposure, the fluid environment, and the pollution degree; each one narrows the family list before the dielectric and thermal numbers do the final pick. [3]
System qualification: the layer supports it; it does not own it
A transformer or machine insulation system is qualified as a combination (paper, film, varnish, and the winding) under UL 1446, and the thermal class belongs to that qualified system, not to any single layer. A substitution, even a like-for-like paper, is a system decision, because the qualification was run on a specific combination. What each converted layer carries is its own documentation: its thermal class, its dielectric strength, its test methods, and lot-code traceability.
Cite the system framework by designation and keep material classes on the part callouts; H-O supplies the layer and its TDS, and the winding house owns the system qualification. [12]
Specification Tools
Two tools to take you from "we're insulating a distribution busbar or transformer" to here's the material direction for the drawing set: a selector that maps thermal class, dielectric field, and mechanical duty to material directions, and a side-by-side comparison of every distribution-insulation family on this page.
1. Distribution-insulation material selector
Set the three axes that pick a distribution-insulation material: the thermal class the part must carry, whether the barrier bends or bears load, and the environment. The selector returns the material directions that fit, with what to send and the citation language. Every direction is also printed in the material reference section, so nothing here exists only behind a script. The default is set for a 220 °C dry-type transformer layer.
A 220 °C (Class R) dry-type layer position points to aramid paper as the backbone, with Kapton® film for the thinnest turn barriers. Values per the TDS; thermal class per IEC 60085, dielectric strength per ASTM D149.
2. Side-by-side: distribution-insulation family comparison matrix
Every family called out on this page, with construction, the property that drives its selection, the standards its TDS cites, and the zone it serves. Click a column header to sort. Click any material name to jump to its accordion entry.
| Material | Construction | Selection property | Standards on the TDS / by designation | Zone | |
|---|---|---|---|---|---|
| Papers (layer, coil, slot) | |||||
| Nomex® 410 / 411 Aramid PaperMeta-aramid paper | Calendered / uncalendered | Thermal class (220 C / R) | IEC 60085; ASTM D149; UL 1446 (system) | Transformer coil / layer | |
| ManniGlas® Glass-Fiber PaperInorganic glass-fiber | Glass-fiber paper | High-temperature barrier | UL 94 (per TDS) | Transformer / thermal | |
| Fish Paper / Vulcanized FibreZnCl2 cellulose fibre | Vulcanized fibre sheet | Dielectric strength (6–10 kV/mm) | NEMA F/FR; ASTM D149 | Slot / washer (LV) | |
| Films (thin, bending barriers) | |||||
| Kapton® Polyimide FilmPolyimide film | Thin film, slit / die-cut | Dielectric strength per gauge | ASTM D149 (per TDS) | Busbar wrap / turn barrier | |
| PEEK Film (APTIV®)PEEK film | Thin film | Long-term thermal (RTI) | UL 746B; ASTM D149 | Demanding film positions | |
| Laminates (load-bearing barriers) | |||||
| G10/FR4 Glass-EpoxyGlass-epoxy laminate | Rigid laminate, machined | Mechanical load + dielectric | NEMA LI 1; UL 94 | Phase barrier / standoff | |
| Durostone® Composite LaminateComposite laminate | Rigid composite | High CTI + 16 kV/mm (EPC 203) | IEC 60243; IEC 60112; UL 94 | MV support insulator | |
| Thermal / inorganic barriers | |||||
| Mica Barrier SheetInorganic mica laminate | Mica laminate sheet | High-temperature / arc barrier | ~700–800 C (per supplier data) | Arc-adjacent / hottest | |
| ArmaGel® Aerogel BlanketSilica aerogel blanket | Flexible aerogel blanket | Thermal resistance / mm | ASTM C177 (per TDS) | Thermal-adjacent barrier | |
Skip ahead and request your engineering review now
If your drawing set already calls out a Nomex® grade, a Kapton® wrap, a mica or ManniGlas® barrier, a G10/FR4 or Durostone® standoff, or fish-paper slot liners, send it over for engineering review against the TDSs and the standards language.
Distribution-insulation failures you can prevent at spec
Distribution insulation fails quietly first: a class that ran hot for years and embrittled, a surface that tracked under pollution, a support that cracked under a fault it was never sized for, a barrier punctured at a field-trimmed edge, or a system qualification that stalled on an undocumented layer. Five patterns cover most of what goes wrong, and each is a specification decision made before the first part is cut.
In distribution equipment, the paperwork is part of the part. A correct material with an undocumented class, or a drawing that claims a system qualification for a single layer, costs more schedule at review than any cutting error. Cite material classes and dielectric strength per TDS, and the insulation system by designation.
Show all 5 failure modes tap to expand
1. Layer paper under-classed, and the winding aged out
A transformer's layer insulation was specified by dielectric strength alone and given a class that matched the nameplate rise but not the real hotspot. For years nothing shows; then the paper embrittles, loses mechanical strength, and a turn-to-turn fault appears far short of design life, because insulation life halves roughly every 10 °C above class. The fix: match the class letter to the winding hotspot, not the average rise.
Aramid paper (Nomex®) carries 220 °C (Class R); step down to thermally-upgraded kraft only where the class allows it. Put the hotspot and target class on the drawing so the paper family is chosen, not assumed. [1]
2. The surface that tracked because creepage was measured as a straight line
A busbar barrier held plenty of clearance and still flashed over, because the number that mattered was creepage, not clearance, and it was measured as a straight line instead of along the surface over the rib.
Under pollution the contaminated surface bridges, a low-CTI material tracks and carbonizes, and the flashover follows the path nobody measured. The fix: take the required creepage from the equipment standard for the voltage and pollution degree (IEC 60664-1 or IEC 62271), measure it along the real surface path including the rib, and choose a high-CTI surface (Durostone®) where the distance is tight.
Die-cut ribs lengthen the surface path without widening the part. [2]
3. The support that cracked under a fault it was never sized for
A phase-barrier standoff was picked as an insulator and forgotten as a structure. Then a short-circuit drives the conductors apart with forces the thin part was never sized for, or a torqued joint cracks the barrier at a bolt hole. The failure is mechanical, and the voltage rating had nothing to say about it. The fix: treat load-bearing barriers as structural members.
Use G10/FR4 (NEMA LI 1) or Durostone® composite sized to the fault current and bolt loads, keep the material and geometry inside the assembly's verification (IEC 61439, IEC 62271, IEEE C37.20.2), and send the fault current and bolt pattern with the drawing. [6]
4. A barrier punctured at a fold or a field-trimmed edge
The barrier's flat-sheet dielectric strength was fine; the part still punctured, because the field is highest at folds, edges, and thin spots, and the datasheet number is measured on clean flat material.
A wrap creased at a busbar edge, or an installer trimmed a liner with a knife and left a nicked edge that became the breakdown site. The fix: add working margin below the flat-sheet dielectric strength for folds and edges, choose the film gauge to the wrap radius (Kapton® where it bends), and the part with clean, sealed edges instead of trimming it on the bench.
The edge quality is where most puncture failures are won or lost. [5]
5. A system qualification that stalled on an undocumented layer
The build was ready and the review stalled, because a drawing note claimed the layer was "UL 1446 qualified," or a layer was substituted like-for-like with no documentation, and the qualification is a system property that belongs to a specific paper/film/varnish combination.
A single layer, however correct, does not carry the system's qualification. The fix: cite the system framework by designation, keep each layer's own class and dielectric strength on the callouts, treat any substitution as a system decision, and hold the TDS and lot-code traceability so the system file is complete.
H-O supplies the layer and its paperwork; the winding house owns the qualification. [12]
Material reference
Detailed specs for the nine distribution-insulation families referenced on this page: the papers (Nomex® aramid, ManniGlas® glass-fiber, fish paper / vulcanized fibre), the films (Kapton® polyimide, PEEK), the laminates (G10/FR4, Durostone® composite), and the inorganic and thermal barriers (mica sheet, ArmaGel® aerogel).
Values are per the maker TDS on file for each grade with the method named; the insulation-system qualification is cited by designation only, with the class belonging to the tested combination. H-O die-cuts, slits, laminates, and kits every family to drawing.
Nomex® 410 / 411 Aramid PaperTransformer layer, coil & lead insulation · 220 C (Class R) backbone · IEC 60085 / ASTM D149

Class belongs to the qualified system, not to any single layer. H-O supplies the converted layer and its TDS; the winding house owns the system qualification.
Kapton® Polyimide FilmBusbar wrap & thin turn barrier · high kV/mm in thin gauge · ASTM D149

Deep dives on film and paper selection across the voltage range live on the sibling busbar, transformer & motor insulation page.
Mica Barrier SheetHigh-temperature / arc-adjacent barrier · inorganic · ~700–800 C continuous

Family-level temperature figures are per supplier data; per-grade values are read from the TDS on file for the selected grade.
G10/FR4 Glass-Epoxy LaminateLoad-bearing phase barriers & standoffs · NEMA LI 1 grades

Send the fault current and bolt pattern with the drawing; the support gets sized to the mechanical load.
Durostone® Composite LaminateMV support insulators · high CTI + 16 kV/mm (EPC 203) · IEC 60243 / 60112

EPC 203's 16 kV/mm is a per-grade TDS value; confirm the grade on file matches the position before final spec.
ManniGlas® Glass-Fiber PaperHigh-temperature barrier & backing paper · inorganic · UL 94 per TDS

UL 94 listings are per the individual grade TDS; read the grade on file for the specific class.
Fish Paper / Vulcanized FibreLV slot liners, washers & end laminations · ~6–10 kV/mm · NEMA F/FR

Dielectric strength is a family-level range; read the grade and gauge on file for the specific value.
PEEK Film (APTIV®)Demanding thin-film positions · long-term thermal (RTI) · UL 746B

RTI and dielectric values are per the maker TDS; read the grade on file for the specific figures.
ArmaGel® Aerogel BlanketThermal barrier near hot distribution equipment · thermal conductivity per ASTM C177

Thermal-conductivity values are per the ArmaGel® TDS; read the grade on file for the specific figures.
AeroZero® Polyimide-Aerogel Film (Blueshift)Dielectric + thermal barrier in one thin film · thermal-adjacent insulation near hot gear
- AZ-TPS 100 · AZ-TPS 101 single- and double-sided silicone-PSA aerogel film, 190–216 µm, UL 94 VTM-0
- AZ-TPS PI 100 polyimide-faced aerogel film, 240 µm, UL 94 VTM-0 — durable outer skin for handling and wear
- AZ-TPS 102 / 103 / 104 low-outgassing acrylic-adhesive configurations, ASTM E595 TML <1% / CVCM <0.1% — the acrylic system carries a lower temperature ceiling than silicone grades, verify on the TDS
- AZ-TPS GR 100 · DualZero TPS GR 201 · QuadZero TPS GR 400 graphite-faced constructions — spread heat along the face while insulating through the thickness (UL 94 VTM-0 film; V-0 laminates)
Power-distribution insulation: engineer-grade FAQ
Twelve of the questions we hear most from substation, distribution-transformer, and switchgear teams. If your question isn't here, send a drawing or call, engineering picks up.
What is Class R 220 C insulation, and how does it relate to the older class letters?
Class R (220 °C) is the current designation for the top thermal class in the IEC 60085 / IEEE C57 letter system. The letters set the continuous hotspot ceiling: A 105, E 120, B 130, F 155, H 180, N 200, R 220 °C. The class is the maximum hotspot temperature the insulation is designed to withstand for its rated life; aramid paper is the 220 °C backbone. Match the class letter to the winding hotspot, because insulation life halves roughly every 10 °C above class. [1]
What is the difference between creepage and clearance in distribution gear?
Clearance is the shortest straight-line distance through air between two conductive parts; creepage is the shortest path along the surface of the insulator between the same two parts. Under pollution the surface path is what flashes over, so creepage usually governs.
Both distances come from the equipment standard's tables (IEC 60664-1 for LV, IEC 62271 for MV), driven by the rated impulse voltage, the pollution degree (industrial is typically PD3), and the material group (CTI per IEC 60112). A rib on a barrier lengthens the surface path without widening the part. [2]
What insulates a distribution busbar, and how is it chosen?
By mechanics. Kapton® polyimide film wraps the bar where the barrier bends and follows the conductor; G10/FR4 or Durostone® barrier sheet stands between phases where the design needs a rigid wall; fish paper handles the economical LV positions. The required creepage and clearance come from the equipment standard for the voltage and pollution degree, and a rib lengthens the surface path. Die-cut edges hold the datasheet dielectric margin that field-trimmed edges lose. [5]
Why aramid paper (Nomex) in a distribution transformer instead of kraft?
Thermal class. Aramid paper (Nomex® 410 / 411) is the 220 °C (Class R) backbone and the standard for dry-type distribution transformers, where the winding runs hotter than cellulose can survive long-term. Thermally-upgraded kraft and pressboard serve the liquid-immersed side under IEEE C57.154 up to a 180 °C class, where the oil carries heat and the economics favor cellulose. The choice follows the class letter and the cooling method, not habit. [1]
What dielectric strength does fish paper have, and where is it used?
Electrical-grade fish paper (vulcanized fibre) has a dielectric strength of roughly 6–10 kV/mm (about 150–250 V/mil depending on gauge), which suits low- to medium-voltage positions. It is made from cellulose treated with zinc chloride and is used for slot liners, insulating washers, end laminations, and small barriers in distribution apparatus, because it can be cleanly into complex geometries without fraying or delaminating at the edges. The two most common grades are NEMA F and NEMA FR. [11]
When do I need a load-bearing laminate instead of a film or paper barrier?
Whenever the insulation also holds the conductor. A standoff, spacer, or structural phase barrier must survive gravity, torque, and short-circuit forces, and thin film cannot do that. Use G10/FR4 glass-epoxy (NEMA LI 1 grades) for most supports, and Durostone® composite where higher tracking resistance and strength are needed (EPC 203: 16 kV/mm per TDS). Size the part to the fault current and bolt pattern, and keep the material and geometry inside the assembly's verification. [6]
What does the comparative tracking index (CTI) have to do with creepage?
CTI (per IEC 60112) measures how well a surface resists tracking, and it sorts materials into groups that set how much creepage the standard demands. A high-CTI surface needs less creepage than a low-CTI one for the same voltage and pollution degree, so a high-CTI material like Durostone® composite keeps the required distance manageable in a compact MV cubicle. Higher rated impulse voltage, heavier pollution, and lower CTI all push the creepage requirement up. [3]
When does the answer turn inorganic (mica, glass-fiber paper)?
When temperature or arc exposure would degrade an organic material. Mica barrier sheet holds roughly 700–800 °C continuous, does not track or carbonize, and is the classic choice for arc-adjacent positions and the hottest transformer turns. ManniGlas® glass-fiber paper is the inorganic barrier and backing paper for high-temperature positions. Both are to the footprint like any other layer; the selection is a temperature-and-arc decision that overrides the dielectric numbers. [10]
Are these materials "UL 1446 qualified"?
No single layer is, and no honest supplier will claim otherwise. UL 1446 qualifies an insulation SYSTEM, the tested combination of paper, film, varnish, and winding, and the thermal class belongs to that qualified system. What each converted layer carries is its own documentation: its thermal class, its dielectric strength, its test methods, and lot-code traceability. The layer supports a qualified system; it does not carry the qualification alone. A substitution, even like-for-like, is a system decision. [12]
Which switchgear standard governs my creepage and clearance?
It depends on voltage and region. Low-voltage assemblies follow IEC 61439 (with the creepage/clearance principles from IEC 60664-1); medium- and high-voltage switchgear follows the IEC 62271 family; North American metal-clad MV gear follows the ANSI/IEEE C37 series, including IEEE C37.20.2. The barriers and supports on this page are built into those listed assemblies, so their material and geometry are constrained by the assembly's verification, not chosen in isolation. Verify the governing edition before final spec. [13]
Does H-O mold or extrude these insulators, or convert them?
H-O and converts sheet, roll, and laminate stock to drawing, and kiss-cut barriers, slit films and papers, machined and laminate supports, and kitted coil-insulation sets. We do not mold or extrude these parts; molded and extruded profiles are coordinated through a partner network. Conversion runs in Winsted, Connecticut under an ISO 9001:2015 certified quality management system with material traceability and lot-code TDS records.
What should I put on the drawing set so the quote comes back right the first time?
The three axes plus the mechanics: the voltage class and rated impulse voltage (Uimp), the pollution degree, the winding hotspot or target thermal class, the dielectric-strength target or governing creepage/clearance, and, for supports, the fault current and bolt pattern.
Add the barrier or wrap geometry and gauge, any adhesive or liner needs, quantities for prototype and production, and the standards language you need on the paperwork (material classes and dielectric strength per TDS; insulation system by designation). "Recommend the layer" is a valid callout: that is what the engineering review is for.
Glossary: terms used on this page
Quick reference for the thermal-class, dielectric, and creepage terminology used throughout. Each entry links to the relevant standard or test method where applicable.
Thermal class / Class R (220 C)
The continuous hotspot temperature an insulation is designed to withstand for its rated life, per IEC 60085 [1]. The letters run A 105, B 130, F 155, H 180, N 200, R 220 °C; Class R is the current top designation, and aramid paper is its backbone.
Creepage
The shortest path along the surface of an insulator between two conductive parts. Under pollution the surface path governs, and the required distance comes from IEC 60664-1 [2] (LV) or IEC 62271 (MV), set by the impulse voltage, pollution degree, and material group.
Clearance
The shortest straight-line distance through air between two conductive parts. Distinct from creepage: creepage ≥ clearance because the surface path is longer, and under pollution creepage is usually the limiting distance.
Comparative tracking index (CTI)
A measure of how well an insulator surface resists tracking, per IEC 60112 [3]. It sorts materials into groups that set the required creepage: a high-CTI surface needs less creepage for the same voltage and pollution degree.
Dielectric strength
The electric field a material withstands before breakdown, in kV/mm, per ASTM D149 [5] or IEC 60243. Measured on clean, flat material, so working margin allows for folds, edges, and thin spots.
Pollution degree
A rating (PD1–PD4, per IEC 60664-1 [2]) of the conductive contamination expected on an insulator surface; an industrial panel or switchboard is typically PD3. Heavier pollution raises the required creepage.
NEMA LI 1 / G-10 / FR-4
The industrial-laminate classification (NEMA LI 1 [6]) that defines the glass-epoxy grades G-10, flame-retardant FR-4, and G-11 used as load-bearing busbar supports, standoffs, and phase barriers.
Vulcanized fibre / fish paper
Cellulose treated with zinc chloride, then washed and pressed into a tough insulating sheet with roughly 6–10 kV/mm dielectric strength ([11]). The classic LV slot-liner, washer, and end-lamination material; cleanly without fraying.
Aramid paper (Nomex)
Meta-aramid paper (Nomex® 410 calendered, 411 uncalendered) with outstanding thermal endurance and mechanical strength; the 220 °C (Class R) backbone for transformer layer, coil, and lead insulation.
Insulation system (UL 1446)
The qualified combination of paper, film, varnish, and winding evaluated together per UL 1446 [12]. The thermal class belongs to the system, so a substitution is a system decision; a single layer supports the system without carrying its qualification.
Relative thermal index (RTI)
A material's long-term thermal-ageing rating, per UL 746B [8]; part of the qualification package for demanding film positions such as PEEK.
Rated impulse voltage (Uimp)
The peak transient (lightning/switching) voltage the insulation must withstand; one of the inputs, with pollution degree and material group, that sets the required creepage and clearance in the IEC 60664-1 [2] tables.
Last updated · Reviewed by H-O Products engineering (ISO 9001:2015 certified converter, Winsted, CT).
Standards, test methods & technical references
The standards, test methods, and maker technical data sheets cited throughout this page. The insulation-system framework (UL 1446) is cited by designation: it qualifies the tested paper/film/varnish combination, and the class belongs to the qualified system. Standards editions current as of July 2026; verify against the publishing body before final spec. H-O materials are aligned to these standards through the source manufacturer's TDS, not independently certified by H-O unless explicitly stated on the quote.
[1] IEC 60085
Electrical insulation — Thermal evaluation and designation. The thermal-class framework (A 105 / B 130 / F 155 / H 180 / N 200 / R 220 °C) used throughout the transformer and coil sections of this page. webstore.iec.ch (IEC 60085)
[2] IEC 60664-1
Insulation coordination for equipment within low-voltage supply systems, Part 1: Principles, requirements and tests. The source of the creepage and clearance tables, pollution degrees, and material groups that frame this page's distances. webstore.iec.ch (IEC 60664-1)
[3] IEC 60112
Method for the determination of the proof and the comparative tracking indices of solid insulating materials. The CTI method behind the material groups; cited on the Durostone® composite TDSs. webstore.iec.ch (IEC 60112)
[4] IEC 60243
Electric strength of insulating materials, Test methods. The breakdown-gradient method behind the kV/mm values on the composite and film TDSs cited here (Durostone® EPC 203: 16 kV/mm per TDS). webstore.iec.ch (IEC 60243)
[5] ASTM D149
Standard Test Method for Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies. The method cited on the polyimide, PEEK, aramid, and fibre TDSs referenced here. astm.org (D149)
[6] NEMA LI 1
Industrial Laminating Thermosetting Products. The grade system that defines G-10, FR-4, and G-11, the designations for the glass-epoxy busbar supports and phase barriers on this page. nema.org (LI 1)
[7] UL 94
Standard for Tests for Flammability of Plastic Materials for Parts in Devices and Appliances. The flame-class listings cited on the ManniGlas®, G10/FR4, and Durostone® TDSs. shopulstandards.com (UL 94)
[8] UL 746B
Polymeric Materials, Long Term Property Evaluations. The long-term thermal-ageing evaluation (RTI) cited on the PEEK (APTIV®) TDS, part of the qualification package for demanding film positions. shopulstandards.com (UL 746B)
[9] Durostone® composite TDS
Manufacturer technical data sheets for the Durostone® composite grades cited on this page (electric strength per IEC 60243, tracking per IEC 60112, thermal endurance per IEC 60216, UL 94 listings; EPC 203 reports 16 kV/mm). Roechling technical library; verify the current grade sheet before final spec.
[10] Film, paper & barrier maker literature
Manufacturer technical libraries for the Nomex® and Kapton® families, Apical® polyimide, APTIV® PEEK film, mica barrier sheet, ManniGlas® glass-fiber paper, and ArmaGel® aerogel; gauge ranges, grade naming, temperature ratings, and test methods per the published data sheets. Values per the TDS on file for the selected grade.
[11] Vulcanized fibre / fish paper (NEMA F/FR)
Electrical-grade vulcanized fibre / fish paper: cellulose treated with zinc chloride; dielectric strength roughly 6–10 kV/mm (about 150–250 V/mil by gauge); NEMA F and NEMA FR grades. Values per the supplier data sheet on file; dielectric strength per ASTM D149. Verify grade and gauge before final spec.
[12] UL 1446
Standard for Systems of Insulating Materials, General. The system-qualification framework for the paper / film / varnish combinations inside transformers and machines; the reason substitutions are system decisions and the class belongs to the qualified system. shopulstandards.com (UL 1446)
[13] IEEE C37.20.2 / IEC 61439 / IEC 62271
The switchgear-assembly standards (IEEE C37.20.2 for metal-clad MV gear; IEC 62271 for HV/MV switchgear; IEC 61439 for LV assemblies) that the supports and barriers on this page are built into. Material selections inside a listed assembly are constrained by its verification. standards.ieee.org
Updated . Standards editions and links current at publication; verify against the publishing body before final spec. H-O converts materials aligned to the methods cited; H-O does not certify insulation systems. Lot-specific documentation available on request.
To review your distribution-insulation design, send:
- Voltage class & rated impulse voltage (Uimp)
- Pollution degree (PD1–PD4)
- Winding hotspot / target thermal class
- Dielectric-strength target or governing creepage/clearance
- Fault current & bolt pattern (for supports)
- Barrier / wrap geometry & gauge
- Adhesive / liner / lamination needs
- Prototype and annual volume
Get a power-distribution insulation engineering quote
Send a drawing set, winding spec, or cubicle layout. We typically respond within one business day with a material recommendation, prototype lead time, and TDS verification against your thermal class, dielectric margin, and creepage/clearance.
See also: related H-O application pages
Engineering content for the adjacent energy and power sub-applications and the parent hub. Each page covers material selection, failure modes, and converter-side process detail for its application family.
Sibling sub-application
Power electronics TIMs & high-temperature insulation
The thermal-interface-material and high-temperature-insulation deep dive behind this page's thermal-adjacent barriers.
Read the page
Sibling sub-application
Arc flash & fire protection
The arc-flash containment and fire-barrier layers for the same gear this page's phase barriers live in.
Read the page
Sibling sub-application
Outdoor power & substation sealing
The gasketing and environmental sealing for outdoor substation and MV enclosures that house this page's insulation.
Read the page
Sibling sub-application
Transformer oil & chemical-resistant sealing
The oil- and chemical-resistant gasketing for liquid-immersed distribution transformers and the enclosures on this page.
Read the page
Sibling sub-application
Busbar, transformer & motor insulation
The OEM / machine edition of this same catalog: the full laminate, mica, aramid, and film story across the voltage range.
Read the page
Industry hub
Energy, power & renewable
The full energy application family: insulation, thermal, EMI, sealing, arc-flash, vibration, and renewable-infrastructure pages.
Read the page
Material data & standards. All thermal-class, dielectric, and temperature values on this page are taken from the source maker's technical data sheets with the method named (ASTM D149; IEC 60085, 60664-1, 60243, 60112, 60216; NEMA LI 1; UL 94, UL 746B classes per the listed grade TDSs).
The insulation-system framework (UL 1446) and the switchgear-assembly standards (IEC 62271, IEC 61439, IEEE C37.20.2) are cited by designation only: they qualify systems and assemblies, the class or listing belongs to the tested combination, and the materials on this page support designs evaluated to them.
H-O converts materials; H-O does not qualify insulation systems or certify switchgear, and does not independently certify materials against the standards unless explicitly stated on the quote. Verify against the maker TDS and your system-level qualification plan.
Conversion scope. H-O and converts sheet, roll, and laminate stock to drawing in Winsted, Connecticut: die-cut and kiss-cut barriers, slit films and papers, machined and laminate supports, waterjet-cut thick sections, laminations, and kitted coil-insulation sets, with material traceability and lot-code TDS records. H-O does not mold or extrude these parts; molded and extruded profiles are coordinated through a partner network. Lead-time and MOQ details are in the process strip and the quote form above.