Doc No PDI-APP-01 Rev 1.0 Updated 2026-07 Document Application Page · Busbar, Transformer & Power Distribution Insulation Classification Public Release
Custom Die-Cut Power-Distribution Insulation · For substation, distribution-transformer & MV/LV switchgear engineers

Custom Busbar, Transformer & Power Distribution Insulation

H-O Products die-cuts and converts aramid paper, polyimide film, mica barrier sheet, glass-epoxy and composite laminate, and fish paper into the busbar barriers, phase supports, transformer layer insulation, and slot liners inside distribution transformers, medium- and low-voltage switchgear, and substation gear, built to your drawing.

Built for: feeder and bus-duct barriers and wrap in MV/LV distribution boards, padmount- and substation-transformer coil and layer insulation, collector-bus barriers in wind and solar plants and BESS-adjacent power blocks, rigid standoffs that hold live conductors apart in switchyards, and the slot, washer, and end-lamination parts that carry the thermal class (up to Class R 220 °C) and the creepage the equipment standard demands.

01
9 families
Distribution-insulation material families
Nomex® aramid paper, Kapton® polyimide film, mica barrier sheet, G10/FR4 and composite laminate, ManniGlas® glass-fiber paper, fish paper / vulcanized fibre, PEEK film, and ArmaGel® aerogel.
02
220°C
Top thermal class this page serves
Class R (220 °C) is the current top designation in the IEC 60085 / IEEE C57 class letter system (A 105, B 130, F 155, H 180, N 200, R 220); aramid paper is the 220 °C backbone.
03
3 axes
Every distribution-insulation part sits on three selection axes
Thermal class (IEC 60085), dielectric strength (ASTM D149 / IEC 60243 per TDS), and creepage/clearance (IEC 60664-1 LV, IEC 62271 MV) verified in the assembly.
04
13
References cited by designation
IEC 60085, IEC 60664-1, IEC 60243, IEC 60112, ASTM D149, NEMA LI 1, UL 1446, UL 94, UL 746B, and the switchgear-assembly family (IEC 62271 / IEC 61439 / IEEE C37.20.2).
LocationMade in Winsted, CT · Family-owned since 1971 · ISO 9001:2015 Certified Organization
Copper busbars and a distribution transformer in a substation with dielectric barriers and paper-wrapped windings
Quick Answer

To insulate power-distribution equipment, select on three axes. Thermal class (IEC 60085 / IEEE C57): match the class letter (A 105 through R 220 °C) to the winding hotspot — Nomex® aramid paper is the 220 °C backbone for transformer layer and coil insulation.

Dielectric strength (ASTM D149 / IEC 60243 per TDS): Kapton® polyimide film where the barrier bends and wraps busbars; fish paper / vulcanized fibre (roughly 6–10 kV/mm) for LV slot liners; Durostone® composite (16 kV/mm per TDS) where the barrier also carries load. Creepage/clearance per IEC 60664-1 / IEC 62271: the surface path governs under pollution, set by pollution degree and material group (CTI per IEC 60112).

The remaining duties are mapped in the When-to-spec list. Values are per the TDS on file; see the material reference below for ordering details.

Standards & Test Methods

Material- and system-level, by designation: IEC 60085 (thermal classes / designation) · IEC 60664-1 (LV insulation coordination: creepage, clearance, pollution degree, material group) · ASTM D149 / IEC 60243 (dielectric breakdown / electric strength) · IEC 60112 (comparative tracking index, CTI) · NEMA LI 1 (industrial laminate grades G-10 / FR-4 / G-11) · UL 1446 (systems of insulating materials) · UL 94 (flammability classes) · UL 746B (long-term polymeric evaluation, RTI) · and the switchgear-assembly family (IEC 62271 for MV, IEC 61439 for LV, IEEE C37.20.2 for metal-clad).

Editions current as of July 2026; verify before final spec.

When To Spec What
Who this is for

This guide is for utility spec engineers, EPC contractors, and generation and switchgear OEMs specifying insulation for substation and switchyard gear, padmount and distribution transformers, feeder and bus-duct runs, and the collector buses that gather wind, solar, and BESS output before it reaches the grid: busbar barriers and wrap, transformer layer and coil insulation, phase-barrier standoffs, and slot/washer parts for MV and LV distribution equipment.

If you build the machine, drive, or switchgear cabinet rather than distribute or collect the power, the busbar, transformer & motor insulation sibling page is the OEM edition of this same catalog.

Finished die-cut Nomex® 410 / 411 Aramid Paper parts converted by H-O Products, on release liner ready to ship
How it works
  1. 1
    Send drawing
    Upload a DXF, STEP, or PDF, or describe the busbar layout, coil, or cubicle. A sample part works too.
  2. 2
    Material review
    Engineering reviews the thermal class, dielectric margin, and creepage/clearance against the maker TDSs, and frames the standards language correctly: material classes and dielectric strength by TDS; thermal class per IEC 60085; creepage per the equipment standard; system qualification (UL 1446) with the tested winding.
  3. 3
    Prototype
    Typically 3–5 business days for common configurations on materials we keep on hand. Standard production 2 weeks; special orders run custom lead times. Made-to-order; MOQ varies by material and part.
  4. 4
    Production
    Standard production runs ship about 2 weeks after drawing approval, on flatbed die-cutting, slitting for wrap and roll stock, and kitting for coil-insulation sets. Ongoing parts run with material traceability and lot-code TDS records.
Prototype-to-Production Insulation Converting · Power-Distribution Insulation Die-Cutting

Voltage class & hotspot → material selection → converted barrier / layer → production supply.

  1. 1
    Voltage class & hotspot
    Rated voltage, impulse withstand (Uimp), and the winding hotspot / thermal class the part must carry.
  2. 2
    Set the three axes
    Thermal class (IEC 60085), dielectric margin (ASTM D149 / IEC 60243), and creepage/clearance (IEC 60664-1 or IEC 62271) for the pollution degree.
  3. 3
    Choose material family
    Paper where it wraps, film where it bends, laminate where it bears load, inorganic sheet where temperature or arc drives it.
  4. 4
    Add adhesive / liner / lamination
    PSA backing, release liner, or multi-layer lamination applied in-house per the drawing.
  5. 5
    Die-cut to drawing
    Clean, sealed edges instead of field-trimmed ones: the edge quality that removes the trim damage that starts most barrier failures.
  6. 6
    Quote prototype or production
    TDS on file and lot-code traceability for the system file, prototype through full production.
Converted Power-Distribution Insulation Materials · Where it lives

Application Zones

Six insulation problems define distribution equipment: the busbar barriers and wrap that hold phase-to-phase and phase-to-ground distance in MV/LV boards; the phase-barrier standoffs that physically support live conductors under fault forces; the distribution-transformer coil and layer insulation that carries the thermal class; the medium-voltage switchgear compartment where creepage and pollution degree govern; the low-voltage slot, washer, and end-lamination parts; and the thermal barriers that live beside hot distribution equipment.

Click a tab to see the stack, the controlling property, and the families H-O converts for that zone.

Die-cut busbar barriers and wrap for distribution gear — a G10 or FR4 barrier panel with slotted phase openings and a bonded creepage rib, a laminate standoff block, two fish-paper barrier strips, and a kiss-cut sheet of amber polyimide busbar wraps on release liner, cut to the board layout by H-O Products.

Busbar barriers & wrap: holding the distance under pollution

Design references: IEC 60664-1 (LV), IEC 62271 (MV) insulation coordinationMaterial methods: ASTM D149, IEC 60243, IEC 60112

A distribution busbar's insulation has one job the voltage makes deceptively simple and the environment makes hard: hold the required distance phase-to-phase and phase-to-ground. Two distances matter, and they are not the same. Clearance is the shortest straight-line gap through air; creepage is the shortest path across the surface of the insulator, and under pollution the surface path is what flashes over.

Kapton® polyimide film wraps the bar where the barrier has to bend and follow the conductor; barrier sheet of glass-epoxy laminate or composite (with a rib that lengthens the surface path) stands between phases where the design needs a rigid wall. The creepage and clearance a board must hold come from the equipment standard's tables (IEC 60664-1 for LV, IEC 62271 for MV), driven by the rated impulse voltage, the pollution degree, and the material group (CTI per IEC 60112).

Die-cutting matters here: a barrier earns its keep only if its edges are clean and its rib is where the drawing put it.

Creepage vs clearance across a distribution-gear barrier A live busbar is isolated from a grounded enclosure by a dielectric barrier with a rib. Clearance is drawn as the shortest straight line through air. True creepage is drawn as the longer path hugging the contaminated surface over and around the rib. A failure callout notes that measuring creepage as a straight line understates the required distance. INSULATION COORDINATION · IEC 60664-1 / IEC 62271 Creepage vs clearance across a busbar barrier GROUNDED ENCLOSURE / EARTH LIVE BUSBAR Die-cut dielectric barrier rib lengthens the surface path Clearance shortest gap through air True creepage shortest path across the surface Creepage ≥ clearance: the surface path is longer, and pollution degree makes it govern. Failure: creepage measured as a straight line — understates distance. Clearance (air) Creepage (surface) Representative — validate in the application.
Kapton® Polyimide Film (busbar wrap)The thin dielectric that bends and wraps the bar; dielectric strength per ASTM D149 on the maker TDS, slit and to the busbar geometry. [5]
G10/FR4 Barrier Sheet (NEMA LI 1)Rigid phase barrier with a rib to lengthen creepage; NEMA LI 1 grade designations, cut to the board layout. [6]
Durostone® Composite (high-CTI barrier)Where the pollution degree needs a high material group: EPC 203 reports 16 kV/mm per the TDS (IEC 60243), with CTI per IEC 60112. [4]
Fish Paper / Vulcanized Fibre (LV wrap)Economical LV barrier and wrap, roughly 6–10 kV/mm (NEMA F/FR grades), without fraying at the edges. [11]
Machined glass-epoxy phase barriers and standoffs — a large G10 or FR4 barrier panel with slot and window cut-outs and bolt holes, three G10 standoff and spacer blocks, and a laminate barrier plate, cut and drilled to the assembly drawing by H-O Products.

Phase barriers & standoffs: the insulation that also carries load

Design references: IEC 61439 / IEC 62271 / IEEE C37.20.2 assembliesMaterial methods: NEMA LI 1, IEC 60243, IEC 60112

Some distribution insulation does more than block current: it holds the conductor in place against gravity, torque, and short-circuit forces. Standoffs, spacers, and structural phase barriers are the load-bearing members of the insulation system, and the material choice is a mechanical one first. Glass-epoxy laminate (G10/FR4, the NEMA LI 1 grades) machines and into supports and barriers with the strength to survive fault forces and bolt loads.

Where the pollution degree or the arc environment pushes harder, Durostone® composite laminate steps up the tracking resistance and electric strength (EPC 203: 16 kV/mm per TDS). These parts live inside listed assemblies (IEC 61439 for LV, IEC 62271 and IEEE C37.20.2 for MV metal-clad gear), so the barrier's material and geometry are constrained by the assembly's verification, not chosen in isolation.

Send the fault current and the bolt pattern with the drawing; the support gets sized to the load it actually carries, not the voltage alone.

G10/FR4 Glass-Epoxy (NEMA LI 1)Load-bearing standoffs, spacers, and phase barriers; NEMA LI 1 grade designations, machined and to drawing. [6]
Durostone® Composite LaminateHigh-CTI, high-strength barriers and supports for MV gear; EPC 203 reports 16 kV/mm per TDS (IEC 60243), UL 94 listings on rated grades. [9]
Mica Barrier Sheet (arc-adjacent)Inorganic barrier where an arc or high temperature would degrade an organic laminate; family holds roughly 700–800 °C continuous per supplier data. [10]
Arc-flash & fire barriers (sibling page)The arc-flash containment and fire-barrier layers for the same gear are covered on the arc flash & fire protection page.
Distribution transformer windings wrapped in aramid layer insulation paper before assembly

Distribution-transformer coil & layer insulation: carrying the thermal class

Thermal-class framing: IEC 60085 / IEEE C57.154 (up to 180 C liquid; 220 C dry with aramid)Material methods: ASTM D149, IEC 60085, UL 1446

Inside a distribution transformer the insulation problem is thermal endurance across decades. Interlayer and conductor-wrap paper separates turns and layers, and its material is chosen by the thermal class: aramid paper (Nomex® 410 calendered, 411 uncalendered) is the backbone of 220 °C (Class R) designs and the standard for dry-type distribution transformers, while thermally-upgraded kraft and pressboard serve the liquid-immersed side under IEEE C57.154 up to a 180 °C class.

Layer insulation is specified by dielectric strength per ASTM D149 and by the class letter that sets the continuous hotspot; life halves roughly every 10 °C above class, so the class match is the whole game. One sentence governs the paperwork: the insulation SYSTEM (paper/film/varnish combination) is qualified per UL 1446, and the class belongs to the qualified system, not to any single layer.

H-O and slits the layer and lead insulation to the winding drawing; the winding house owns the system qualification.

Nomex® 410 / 411 Aramid PaperLayer, conductor-wrap, and lead insulation; the 220 °C (Class R) backbone, calendered (410) and uncalendered (411) per the maker TDS. [1]
Kapton® Polyimide FilmThin high-dielectric barrier for turn and lead insulation where gauge is tight; dielectric strength per ASTM D149 on the TDS. [5]
Mica Barrier SheetHigh-temperature turn and barrier insulation for the hottest positions; inorganic, dimensionally stable at flame temperatures. [10]
ManniGlas® Glass-Fiber PaperHigh-temperature barrier and backing paper; inorganic glass-fiber sheet with UL 94 listings per the maker TDS. [7]
Interior of a medium-voltage switchgear cubicle with insulated busbars and barrier partitions

MV switchgear insulation: creepage and pollution degree govern

Design references: IEC 62271, IEEE C37.20.2 metal-clad gearMaterial methods: IEC 60112 (CTI), IEC 60243, IEC 60664-1

In a medium-voltage cubicle the voltage is high enough that the surface path, not the air gap, is usually the limiting distance, and the material group (CTI per IEC 60112) directly sets how much creepage the standard demands.

The insulation here is a mix of thin barrier and load-bearing support: Durostone® composite and G10/FR4 make the compartment barriers and support insulators that hold the bus in metal-clad gear (IEC 62271, IEEE C37.20.2), while mica and ManniGlas® handle the positions where arc exposure or temperature turns the answer inorganic.

The compartment's creepage and clearance are verified in the assembly against the equipment standard; the material's job is to bring a high enough CTI and dielectric strength that the required distances stay manageable in a compact cubicle. Higher rated impulse voltage, heavier pollution, and lower CTI all demand more distance, so the material choice and the geometry trade against each other.

Durostone® Composite (support insulators)Compartment barriers and support insulators for metal-clad MV gear; high CTI and 16 kV/mm (EPC 203) per TDS. [3]
G10/FR4 Glass-EpoxyBarrier partitions and standoffs inside the cubicle; NEMA LI 1 grades machined and die-cut. [6]
Mica Barrier SheetArc-adjacent barriers at the contact and interrupter positions; inorganic surface that does not track or carbonize. [10]
Enclosure sealing (sibling page)The gasketing and environmental sealing for outdoor substation and MV enclosures is covered on the outdoor power & substation sealing page.
fish paper and vulcanized fibre insulating washers and slot liners for low-voltage apparatus

Slot, washer & end lamination: the LV workhorse parts

Material methods: dielectric strength per ASTM D149 / V-per-mil per TDSDuty: slot liners, washers, end laminations, barriers

The low-voltage side of distribution apparatus runs on parts that are ordinary in form and precise in fit: slot liners, insulating washers, end laminations, and small barriers. Fish paper and vulcanized fibre (ZnCl2-treated cellulose, NEMA F/FR grades) are the classic material here, with dielectric strength around 6–10 kV/mm (roughly 150–250 V/mil depending on gauge) and enough tensile strength to be into complex geometries without fraying or delaminating at the edges.

Where the position needs a thinner or more thermally durable film, Kapton® polyimide and PEEK film (APTIV®, with RTI per UL 746B) take over. The whole value of these parts is edge quality and fit: a liner that covers the slot and survives insertion, cut from the drawing rather than trimmed on the bench.

Fish Paper / Vulcanized Fibre (NEMA F/FR)Slot liners, insulating washers, and end laminations; roughly 6–10 kV/mm, clean edges without fraying. [11]
Kapton® Polyimide FilmThin, high-dielectric film for tight barrier and washer positions; dielectric strength per ASTM D149 on the TDS. [5]
PEEK Film (APTIV®)Demanding thin-film positions where long-term thermal ageing matters; RTI per UL 746B, dielectric per ASTM D149 on the TDS. [8]
G10/FR4 (small barriers & washers)Rigid washers, spacers, and small barriers where the part carries a mechanical load; NEMA LI 1 grades. [6]

Thermal-adjacent barriers: keeping heat off the neighbors

Material methods: thermal conductivity per ASTM C177 on the TDSDuty: thermal barriers near hot distribution equipment

Not every insulation problem in distribution gear is electrical. Where a transformer, reactor, or resistor runs hot next to temperature-sensitive equipment or an enclosure wall, a thermal barrier buys the most temperature drop per millimeter. ArmaGel® aerogel blanket (our blanket-format aerogel line) is the flexible high-resistance barrier for these positions, with thermal conductivity reported per ASTM C177 on its TDS. Where the same duty has to fit in a few mils, Blueshift AeroZero® polyimide-aerogel film carries the thin-film tier — see the material reference below.

Mica and ManniGlas® glass-fiber paper double as thermal barriers where the surface also has to be inorganic and dimensionally stable at high temperature. These are and converted to the panel or wrap geometry like any other layer; the selection is a heat-flux and gap-budget decision, not a dielectric one.

ArmaGel® Aerogel BlanketFlexible high-resistance thermal barrier near hot distribution equipment; thermal conductivity per ASTM C177 on the TDS. [10]
ManniGlas® Glass-Fiber PaperInorganic high-temperature barrier and backing paper; UL 94 listings per the maker TDS. [7]
Mica Barrier SheetInorganic thermal-and-dielectric barrier at the hottest positions; holds roughly 700–800 °C continuous per supplier data. [10]
Power TIMs & thermal management (sibling page)The thermal-interface-material and high-temperature-insulation deep dive lives on the power systems thermal management page.
Spec discipline

Six decisions that drive your distribution-insulation spec

A distribution-insulation part is a single-purpose layer with one or two controlling properties. Miss one and the failure is rarely immediate: a class runs hot and embrittles, a surface tracks under pollution, a support cracks under fault, or a system qualification stalls on a layer nobody can document.

Specification principle

Layers carry classes and dielectric strength; systems carry qualifications. A thermal class (IEC 60085) and a dielectric strength (ASTM D149) belong to a material grade per its TDS. The insulation SYSTEM qualification (UL 1446) belongs to the tested paper/film/varnish combination inside the transformer or machine.

Write material classes and dielectric strength on the part callouts, cite the system framework by designation, and never let a drawing imply that a layer is "UL 1446 qualified" on its own: the layer supports a qualified system.

Class R 220 °C
The current top thermal-class designation your paper choice answers to

The IEC 60085 / IEEE C57 class letters set the continuous hotspot ceiling: A 105, B 130, F 155, H 180, N 200, R 220 °C. Aramid paper is the 220 °C backbone; match the class letter to the winding hotspot, because insulation life halves roughly every 10 °C above class.

Nomex® 410 Aramid Paper Thermal classClass R 220 °C (per TDS) MethodsIEC 60085; ASTM D149 RoleLayer, coil, lead insulation FormDie-cut / slit sheet & roll

Read the six factors below in order. The first three set the electrical spec (thermal class, dielectric margin, creepage/clearance); the next two add mechanics and environment; the last one closes the paperwork. Every factor names its test method, because in this application the documentation is part of the part.

Show all 6 selection factors tap to expand
1

Thermal class: match the letter to the hotspot, not to habit

The insulation class is the continuous hotspot ceiling, and it decides the paper before anything else does. The IEC 60085 / IEEE C57 letters run A 105, B 130, F 155, H 180, N 200, R 220 °C; aramid paper (Nomex®) is the 220 °C backbone, thermally-upgraded kraft serves the liquid-immersed side to a 180 °C class under IEEE C57.154, and mica or glass-fiber paper carries the positions above that.

Life halves roughly every 10 °C over class, so an under-classed paper is a design that quietly ages out. Put the winding hotspot and the target class letter on the drawing; the paper family falls out of that number. [1]

Class is a system property qualified per UL 1446; the layer's class is its contribution to that system.
2

Dielectric margin: strength per gauge, read at the fold

Dielectric strength (kV/mm, per ASTM D149 or IEC 60243 on the TDS) sets the puncture margin, but the number on the datasheet is measured on flat, clean material. Real barriers fail at folds, edges, and thin spots, so the working margin sits below the flat-sheet figure.

The split is by mechanics: thin film where the barrier bends (Kapton®, high kV/mm in thin gauge), fish paper or aramid where a conformable sheet suits the position (roughly 6–10 kV/mm for fibre), and composite where the barrier also carries load (Durostone® EPC 203: 16 kV/mm per TDS).

Specify the gauge and the dielectric strength by grade, and add margin for folds and edges. [5]

Clean edges hold the datasheet margin; field-trimmed edges are where most puncture failures start.
3

Creepage & clearance: the surface path governs under pollution

Clearance is the shortest gap through air; creepage is the shortest path across the insulator surface, and under pollution the surface path is what flashes over. The distances come from the equipment standard's tables (IEC 60664-1 for LV, IEC 62271 for MV), driven by the rated impulse voltage, the pollution degree (industrial is typically PD3), and the material group set by the comparative tracking index (CTI, per IEC 60112).

A high-CTI surface (Durostone®) needs less creepage than a low-CTI one for the same voltage, and a rib on a barrier lengthens the surface path without widening the part. State the voltage class, Uimp, and pollution degree; the required creepage and clearance follow. [2]

The classic error: measuring creepage as a straight line and undersizing the barrier (see the busbar-zone diagram).
4

Mechanical load: film insulates, laminate bears

A phase barrier or standoff that also holds the conductor is a structural member, and thin film cannot do that job. Where the insulation carries gravity, torque, or short-circuit force, the answer is load-bearing laminate: G10/FR4 glass-epoxy (NEMA LI 1 grades) for most supports, Durostone® composite where higher tracking resistance and strength are needed. These parts sit inside listed assemblies (IEC 61439, IEC 62271, IEEE C37.20.2), so the barrier's material and geometry are constrained by the assembly's verification.

Send the fault current and the bolt pattern with the drawing; the support gets sized to the mechanical load, not the voltage alone. [6]

Deep dive on load-bearing barriers and standoffs lives on the sibling busbar, transformer & motor insulation page.
5

Environment: temperature, arc, oil, and pollution pick the chemistry

The distribution environment filters the material family before performance does. Temperature and arc exposure push the answer inorganic (mica sheet, ManniGlas® glass-fiber paper) where an organic laminate would carbonize or track. Oil-immersed distribution transformers need materials compatible with mineral or ester fluid, and thermally-upgraded kraft and pressboard serve that side.

Heavy pollution raises the creepage demand and rewards a high-CTI surface. Name the temperature, any arc exposure, the fluid environment, and the pollution degree; each one narrows the family list before the dielectric and thermal numbers do the final pick. [3]

Oil and chemical-resistant sealing for the same equipment is on the transformer oil & chemical-resistant sealing sibling page.
6

System qualification: the layer supports it; it does not own it

A transformer or machine insulation system is qualified as a combination (paper, film, varnish, and the winding) under UL 1446, and the thermal class belongs to that qualified system, not to any single layer. A substitution, even a like-for-like paper, is a system decision, because the qualification was run on a specific combination. What each converted layer carries is its own documentation: its thermal class, its dielectric strength, its test methods, and lot-code traceability.

Cite the system framework by designation and keep material classes on the part callouts; H-O supplies the layer and its TDS, and the winding house owns the system qualification. [12]

"Recommend the layer" is a valid callout: engineering matches the grade to the class, field, and creepage you send.
Decision support
Instrumentation·Interactive Selection

Specification Tools

Two tools to take you from "we're insulating a distribution busbar or transformer" to here's the material direction for the drawing set: a selector that maps thermal class, dielectric field, and mechanical duty to material directions, and a side-by-side comparison of every distribution-insulation family on this page.

1. Distribution-insulation material selector

Set the three axes that pick a distribution-insulation material: the thermal class the part must carry, whether the barrier bends or bears load, and the environment. The selector returns the material directions that fit, with what to send and the citation language. Every direction is also printed in the material reference section, so nothing here exists only behind a script. The default is set for a 220 °C dry-type transformer layer.

Direction: aramid paper (Nomex® 410 / 411) for the layer

A 220 °C (Class R) dry-type layer position points to aramid paper as the backbone, with Kapton® film for the thinnest turn barriers. Values per the TDS; thermal class per IEC 60085, dielectric strength per ASTM D149.

Send with the drawing: winding hotspot / class letter, gauge, dielectric-strength target, and the wrap or slot geometry.
The selector points to material directions only. It does not set creepage/clearance distances (those come from the equipment standard for your voltage and pollution degree) or qualify an insulation system. H-O supplies the layer, the TDS, and lot-code traceability behind it.

2. Side-by-side: distribution-insulation family comparison matrix

Every family called out on this page, with construction, the property that drives its selection, the standards its TDS cites, and the zone it serves. Click a column header to sort. Click any material name to jump to its accordion entry.

Filter
Material Construction Selection property Standards on the TDS / by designation Zone
Papers (layer, coil, slot)
Nomex® 410 / 411 Aramid PaperMeta-aramid paper Calendered / uncalendered Thermal class (220 C / R) IEC 60085; ASTM D149; UL 1446 (system) Transformer coil / layer
ManniGlas® Glass-Fiber PaperInorganic glass-fiber Glass-fiber paper High-temperature barrier UL 94 (per TDS) Transformer / thermal
Fish Paper / Vulcanized FibreZnCl2 cellulose fibre Vulcanized fibre sheet Dielectric strength (6–10 kV/mm) NEMA F/FR; ASTM D149 Slot / washer (LV)
Films (thin, bending barriers)
Kapton® Polyimide FilmPolyimide film Thin film, slit / die-cut Dielectric strength per gauge ASTM D149 (per TDS) Busbar wrap / turn barrier
PEEK Film (APTIV®)PEEK film Thin film Long-term thermal (RTI) UL 746B; ASTM D149 Demanding film positions
Laminates (load-bearing barriers)
G10/FR4 Glass-EpoxyGlass-epoxy laminate Rigid laminate, machined Mechanical load + dielectric NEMA LI 1; UL 94 Phase barrier / standoff
Durostone® Composite LaminateComposite laminate Rigid composite High CTI + 16 kV/mm (EPC 203) IEC 60243; IEC 60112; UL 94 MV support insulator
Thermal / inorganic barriers
Mica Barrier SheetInorganic mica laminate Mica laminate sheet High-temperature / arc barrier ~700–800 C (per supplier data) Arc-adjacent / hottest
ArmaGel® Aerogel BlanketSilica aerogel blanket Flexible aerogel blanket Thermal resistance / mm ASTM C177 (per TDS) Thermal-adjacent barrier
Notes. Selection properties are family-level descriptors; per-grade values live on the maker TDSs with the methods named. System qualification (UL 1446) appears by designation only: it qualifies the tested paper/film/varnish combination, the class belongs to the qualified system, and the materials here support systems evaluated to it. This matrix is a selection aid; the TDS on file governs for the selected grade.
Found your candidate family? The fastest next step is the drawing: H-O reviews it against these selections and comes back with a manufacturable option and the TDS.
Already know your spec?

Skip ahead and request your engineering review now

If your drawing set already calls out a Nomex® grade, a Kapton® wrap, a mica or ManniGlas® barrier, a G10/FR4 or Durostone® standoff, or fish-paper slot liners, send it over for engineering review against the TDSs and the standards language.

What goes wrong in the field

Distribution-insulation failures you can prevent at spec

Distribution insulation fails quietly first: a class that ran hot for years and embrittled, a surface that tracked under pollution, a support that cracked under a fault it was never sized for, a barrier punctured at a field-trimmed edge, or a system qualification that stalled on an undocumented layer. Five patterns cover most of what goes wrong, and each is a specification decision made before the first part is cut.

Field caution

In distribution equipment, the paperwork is part of the part. A correct material with an undocumented class, or a drawing that claims a system qualification for a single layer, costs more schedule at review than any cutting error. Cite material classes and dielectric strength per TDS, and the insulation system by designation.

Show all 5 failure modes tap to expand

1. Layer paper under-classed, and the winding aged out

A transformer's layer insulation was specified by dielectric strength alone and given a class that matched the nameplate rise but not the real hotspot. For years nothing shows; then the paper embrittles, loses mechanical strength, and a turn-to-turn fault appears far short of design life, because insulation life halves roughly every 10 °C above class. The fix: match the class letter to the winding hotspot, not the average rise.

Aramid paper (Nomex®) carries 220 °C (Class R); step down to thermally-upgraded kraft only where the class allows it. Put the hotspot and target class on the drawing so the paper family is chosen, not assumed. [1]

2. The surface that tracked because creepage was measured as a straight line

A busbar barrier held plenty of clearance and still flashed over, because the number that mattered was creepage, not clearance, and it was measured as a straight line instead of along the surface over the rib.

Under pollution the contaminated surface bridges, a low-CTI material tracks and carbonizes, and the flashover follows the path nobody measured. The fix: take the required creepage from the equipment standard for the voltage and pollution degree (IEC 60664-1 or IEC 62271), measure it along the real surface path including the rib, and choose a high-CTI surface (Durostone®) where the distance is tight.

Die-cut ribs lengthen the surface path without widening the part. [2]

3. The support that cracked under a fault it was never sized for

A phase-barrier standoff was picked as an insulator and forgotten as a structure. Then a short-circuit drives the conductors apart with forces the thin part was never sized for, or a torqued joint cracks the barrier at a bolt hole. The failure is mechanical, and the voltage rating had nothing to say about it. The fix: treat load-bearing barriers as structural members.

Use G10/FR4 (NEMA LI 1) or Durostone® composite sized to the fault current and bolt loads, keep the material and geometry inside the assembly's verification (IEC 61439, IEC 62271, IEEE C37.20.2), and send the fault current and bolt pattern with the drawing. [6]

4. A barrier punctured at a fold or a field-trimmed edge

The barrier's flat-sheet dielectric strength was fine; the part still punctured, because the field is highest at folds, edges, and thin spots, and the datasheet number is measured on clean flat material.

A wrap creased at a busbar edge, or an installer trimmed a liner with a knife and left a nicked edge that became the breakdown site. The fix: add working margin below the flat-sheet dielectric strength for folds and edges, choose the film gauge to the wrap radius (Kapton® where it bends), and the part with clean, sealed edges instead of trimming it on the bench.

The edge quality is where most puncture failures are won or lost. [5]

5. A system qualification that stalled on an undocumented layer

The build was ready and the review stalled, because a drawing note claimed the layer was "UL 1446 qualified," or a layer was substituted like-for-like with no documentation, and the qualification is a system property that belongs to a specific paper/film/varnish combination.

A single layer, however correct, does not carry the system's qualification. The fix: cite the system framework by designation, keep each layer's own class and dielectric strength on the callouts, treat any substitution as a system decision, and hold the TDS and lot-code traceability so the system file is complete.

H-O supplies the layer and its paperwork; the winding house owns the qualification. [12]

Reference

Material reference

Detailed specs for the nine distribution-insulation families referenced on this page: the papers (Nomex® aramid, ManniGlas® glass-fiber, fish paper / vulcanized fibre), the films (Kapton® polyimide, PEEK), the laminates (G10/FR4, Durostone® composite), and the inorganic and thermal barriers (mica sheet, ArmaGel® aerogel).

Values are per the maker TDS on file for each grade with the method named; the insulation-system qualification is cited by designation only, with the class belonging to the tested combination. H-O die-cuts, slits, laminates, and kits every family to drawing.

Nomex® 410 / 411 Aramid PaperTransformer layer, coil & lead insulation · 220 C (Class R) backbone · IEC 60085 / ASTM D149
CompositionMeta-aramid (calendered) paper; the transformer/machine insulation workhorse
Grades hereNomex® 410 (calendered), 411 (uncalendered); pressboard and laminate grades in the same family per the maker literature
Thermal classClass R 220 °C backbone per IEC 60085; the standard for dry-type distribution transformers
MethodsIEC 60085 thermal designation; ASTM D149 dielectric strength per the TDS
Defining propertyThermal endurance with mechanical toughness: holds the class across decades of service
Form factorsDie-cut and slit layer, wrap, and lead insulation; roll and sheet
Where it lives in this application: between turns and layers of a distribution-transformer winding, and as lead and ground insulation. Specified by the thermal class it must carry and the dielectric strength per gauge, cut to the winding drawing. The insulation system it belongs to is qualified as a combination (UL 1446); the paper carries its own class into that system.

Class belongs to the qualified system, not to any single layer. H-O supplies the converted layer and its TDS; the winding house owns the system qualification.

Kapton® Polyimide FilmBusbar wrap & thin turn barrier · high kV/mm in thin gauge · ASTM D149
CompositionPolyimide film (Kapton® / Apical® families)
Grades hereGeneral-purpose HN and the heat-sealable FN designations; gauge range per the maker TDS
Why filmThin, high dielectric strength per gauge, and flexible enough to wrap busbars and line tight barriers
MethodsASTM D149 dielectric strength; thermal endurance per the maker TDS (~400 °C short-term)
Form factorsSlit rolls, wraps and barriers, laminated constructions
Where it lives in this application: wrapping a distribution busbar and lining the tight turn and lead barriers where a rigid sheet cannot follow the geometry. Gauge is chosen to the wrap radius so the film does not crease at edges; dielectric strength is read per ASTM D149 on the TDS with margin for folds.

Deep dives on film and paper selection across the voltage range live on the sibling busbar, transformer & motor insulation page.

Mica Barrier SheetHigh-temperature / arc-adjacent barrier · inorganic · ~700–800 C continuous
CompositionMica paper laminate sheet (muscovite / phlogopite chemistry family)
Why micaInorganic, dimensionally stable at flame temperatures, and does not track or carbonize on the surface
TemperatureFamily rated roughly 700–800 °C continuous with higher peak capability per the supplier data
Related gradesMuscovite and phlogopite rigid / flexible sheet for arc and high-temperature barrier duty
Form factorsDie-cut barriers, slot and channel pieces, laminated stacks
Where it lives in this application: the hottest and arc-adjacent positions in transformers and MV switchgear, where an organic laminate would carbonize or track. Die-cutting matters here: the barrier earns its keep only if it covers the footprint and survives assembly handling, so edges and tolerances come off the drawing.

Family-level temperature figures are per supplier data; per-grade values are read from the TDS on file for the selected grade.

G10/FR4 Glass-Epoxy LaminateLoad-bearing phase barriers & standoffs · NEMA LI 1 grades
CompositionGlass-fabric / epoxy laminate; the NEMA LI 1 industrial-laminate grades
Grades hereG-10 and flame-retardant FR-4 (and G-11 where higher-temperature strength is needed) per NEMA LI 1
Why laminateThe insulation that also carries load: strength to survive fault forces and bolt loads
MethodsNEMA LI 1 grade designations; UL 94 flame class and dielectric per the grade TDS
Form factorsMachined and standoffs, spacers, barriers, and washers
Where it lives in this application: the structural members of the insulation system, standoffs, spacers, and phase barriers that hold live conductors apart inside LV and MV assemblies. Sized to the fault current and bolt pattern, not the voltage alone, and kept inside the assembly's verification (IEC 61439 / IEC 62271).

Send the fault current and bolt pattern with the drawing; the support gets sized to the mechanical load.

Durostone® Composite LaminateMV support insulators · high CTI + 16 kV/mm (EPC 203) · IEC 60243 / 60112
CompositionGlass-reinforced composite laminate (Durostone® EPC / UPM grade families)
Grades hereEPC 203 (reports 16 kV/mm per TDS) and the UPM grades with UL 94 listings per the maker TDS
Electric strength16 kV/mm on the EPC 203 TDS (IEC 60243); CTI / material group per IEC 60112
MethodsIEC 60243 electric strength; IEC 60112 tracking; IEC 60216 thermal endurance; UL 94
Form factorsMachined and support insulators, compartment barriers, and standoffs
Where it lives in this application: the support insulators and compartment barriers of metal-clad MV switchgear, where the pollution degree needs a high material group (CTI) and the fault forces need strength. The 16 kV/mm and CTI figures on the TDS keep the required creepage manageable in a compact cubicle.

EPC 203's 16 kV/mm is a per-grade TDS value; confirm the grade on file matches the position before final spec.

ManniGlas® Glass-Fiber PaperHigh-temperature barrier & backing paper · inorganic · UL 94 per TDS
CompositionInorganic glass-fiber paper (ManniGlas® family)
Why glass-fiberHigh-temperature, inorganic surface for barrier and backing duty where organic paper would degrade
Standards languageUL 94 listings per the individual grade TDS
Related useBacking and barrier paper adjacent to hot transformer and reactor surfaces
Form factorsDie-cut barriers, backing sheet, laminated constructions
Where it lives in this application: the high-temperature barrier and backing positions in transformers and near hot distribution equipment, where a thin, inorganic, dimensionally stable paper is needed. Die-cut and converted to the panel or wrap geometry like any other layer.

UL 94 listings are per the individual grade TDS; read the grade on file for the specific class.

Fish Paper / Vulcanized FibreLV slot liners, washers & end laminations · ~6–10 kV/mm · NEMA F/FR
CompositionVulcanized fibre: cellulose treated with zinc chloride, then washed and pressed
Grades hereElectrical-grade fish paper; NEMA F and NEMA FR vulcanized-fibre grades
Dielectric strengthRoughly 6–10 kV/mm (about 150–250 V/mil depending on gauge) per the supplier data
Why fibreCleanly into complex geometries (slot liners, washers, laminations) without fraying or delaminating
Form factorsDie-cut slot liners, insulating washers, end laminations, small barriers
Where it lives in this application: the low-voltage workhorse parts, slot liners, insulating washers, and end laminations in distribution apparatus. The whole value is edge quality and fit: a liner that covers the slot and survives insertion, cut from the drawing rather than trimmed on the bench.

Dielectric strength is a family-level range; read the grade and gauge on file for the specific value.

PEEK Film (APTIV®)Demanding thin-film positions · long-term thermal (RTI) · UL 746B
CompositionPolyetheretherketone (PEEK) film (APTIV® family)
Why PEEKHigh relative thermal index and mechanical strength for demanding thin-film insulation positions
Standards languageRTI per UL 746B; dielectric strength per ASTM D149 on the TDS
Related filmsPolyimide (Kapton®) where lower cost suits; PEEK where long-term ageing and strength drive the choice
Form factorsSlit rolls, barriers and washers, laminated constructions
Where it lives in this application: the thin-film positions where long-term thermal ageing and mechanical strength matter more than cost, part of the qualification package for demanding barrier and washer positions. Die-cut and slit to the drawing.

RTI and dielectric values are per the maker TDS; read the grade on file for the specific figures.

ArmaGel® Aerogel BlanketThermal barrier near hot distribution equipment · thermal conductivity per ASTM C177
CompositionSilica aerogel in a flexible fiber web (ArmaGel® HT / HTL family)
Why aerogelThe most thermal resistance per millimeter of any flexible blanket, for tight thermal-barrier positions
MethodsThermal conductivity per ASTM C177; surface burning per ASTM E84 where reported on the TDS
Product-line noteArmaGel® is our blanket-format aerogel line; Blueshift AeroZero® covers the thin-film tier
Form factorsDie-cut panels, wraps, and barrier pieces on the blanket
Where it lives in this application: the thermal barrier between hot distribution equipment (transformers, reactors, resistors) and temperature-sensitive neighbors or enclosure walls. The selection is a heat-flux and gap-budget decision, not a dielectric one; to the panel or wrap geometry.

Thermal-conductivity values are per the ArmaGel® TDS; read the grade on file for the specific figures.

AeroZero® Polyimide-Aerogel Film (Blueshift)Dielectric + thermal barrier in one thin film · thermal-adjacent insulation near hot gear
Composition Blueshift AeroZero® polyimide aerogel film — polyimide chemistry, roughly 85% air by volume; silicone- or acrylic-PSA backed
Best jobs Thermal-adjacent dielectric barriers near transformers, reactors and hot busbar runs — where Kapton-class film insulates electrically but passes heat straight through
Dielectric role Dielectric polyimide construction; per-grade dielectric strength is not published for every configuration — verify on the TDS before assigning voltage duty
Temperature Glass transition 305 °C; decomposition 380–470 °C on silicone constructions, roughly 255–275 °C on acrylic-adhesive grades, per manufacturer data
Flame UL 94 VTM-0 films; V-0 laminates on rated grades
Best fit Low-clamp-load positions; compression behavior under sustained bolt load is not published, so keep it out of high-pressure joints
Form factors Roll stock to 12 in wide, slit to 4 mm; die-cut wraps, barriers and interleaves, adhesive-backed
Grades commonly converted
  • AZ-TPS 100 · AZ-TPS 101 single- and double-sided silicone-PSA aerogel film, 190–216 µm, UL 94 VTM-0
  • AZ-TPS PI 100 polyimide-faced aerogel film, 240 µm, UL 94 VTM-0 — durable outer skin for handling and wear
  • AZ-TPS 102 / 103 / 104 low-outgassing acrylic-adhesive configurations, ASTM E595 TML <1% / CVCM <0.1% — the acrylic system carries a lower temperature ceiling than silicone grades, verify on the TDS
  • AZ-TPS GR 100 · DualZero TPS GR 201 · QuadZero TPS GR 400 graphite-faced constructions — spread heat along the face while insulating through the thickness (UL 94 VTM-0 film; V-0 laminates)
Where it lives in this application the bridge between the film rack and the aerogel shelf. It carries Kapton-class dielectric duty while adding blanket-class thermal function per millimeter, thin enough to wrap and die-cut like the films above it. Confirm grade-level values against Blueshift’s current technical data sheets.
Engineering questions

Power-distribution insulation: engineer-grade FAQ

Twelve of the questions we hear most from substation, distribution-transformer, and switchgear teams. If your question isn't here, send a drawing or call, engineering picks up.

12 questions · click a question to expand its answer

What is Class R 220 C insulation, and how does it relate to the older class letters?

Class R (220 °C) is the current designation for the top thermal class in the IEC 60085 / IEEE C57 letter system. The letters set the continuous hotspot ceiling: A 105, E 120, B 130, F 155, H 180, N 200, R 220 °C. The class is the maximum hotspot temperature the insulation is designed to withstand for its rated life; aramid paper is the 220 °C backbone. Match the class letter to the winding hotspot, because insulation life halves roughly every 10 °C above class. [1]

What is the difference between creepage and clearance in distribution gear?

Clearance is the shortest straight-line distance through air between two conductive parts; creepage is the shortest path along the surface of the insulator between the same two parts. Under pollution the surface path is what flashes over, so creepage usually governs.

Both distances come from the equipment standard's tables (IEC 60664-1 for LV, IEC 62271 for MV), driven by the rated impulse voltage, the pollution degree (industrial is typically PD3), and the material group (CTI per IEC 60112). A rib on a barrier lengthens the surface path without widening the part. [2]

What insulates a distribution busbar, and how is it chosen?

By mechanics. Kapton® polyimide film wraps the bar where the barrier bends and follows the conductor; G10/FR4 or Durostone® barrier sheet stands between phases where the design needs a rigid wall; fish paper handles the economical LV positions. The required creepage and clearance come from the equipment standard for the voltage and pollution degree, and a rib lengthens the surface path. Die-cut edges hold the datasheet dielectric margin that field-trimmed edges lose. [5]

Why aramid paper (Nomex) in a distribution transformer instead of kraft?

Thermal class. Aramid paper (Nomex® 410 / 411) is the 220 °C (Class R) backbone and the standard for dry-type distribution transformers, where the winding runs hotter than cellulose can survive long-term. Thermally-upgraded kraft and pressboard serve the liquid-immersed side under IEEE C57.154 up to a 180 °C class, where the oil carries heat and the economics favor cellulose. The choice follows the class letter and the cooling method, not habit. [1]

What dielectric strength does fish paper have, and where is it used?

Electrical-grade fish paper (vulcanized fibre) has a dielectric strength of roughly 6–10 kV/mm (about 150–250 V/mil depending on gauge), which suits low- to medium-voltage positions. It is made from cellulose treated with zinc chloride and is used for slot liners, insulating washers, end laminations, and small barriers in distribution apparatus, because it can be cleanly into complex geometries without fraying or delaminating at the edges. The two most common grades are NEMA F and NEMA FR. [11]

When do I need a load-bearing laminate instead of a film or paper barrier?

Whenever the insulation also holds the conductor. A standoff, spacer, or structural phase barrier must survive gravity, torque, and short-circuit forces, and thin film cannot do that. Use G10/FR4 glass-epoxy (NEMA LI 1 grades) for most supports, and Durostone® composite where higher tracking resistance and strength are needed (EPC 203: 16 kV/mm per TDS). Size the part to the fault current and bolt pattern, and keep the material and geometry inside the assembly's verification. [6]

What does the comparative tracking index (CTI) have to do with creepage?

CTI (per IEC 60112) measures how well a surface resists tracking, and it sorts materials into groups that set how much creepage the standard demands. A high-CTI surface needs less creepage than a low-CTI one for the same voltage and pollution degree, so a high-CTI material like Durostone® composite keeps the required distance manageable in a compact MV cubicle. Higher rated impulse voltage, heavier pollution, and lower CTI all push the creepage requirement up. [3]

When does the answer turn inorganic (mica, glass-fiber paper)?

When temperature or arc exposure would degrade an organic material. Mica barrier sheet holds roughly 700–800 °C continuous, does not track or carbonize, and is the classic choice for arc-adjacent positions and the hottest transformer turns. ManniGlas® glass-fiber paper is the inorganic barrier and backing paper for high-temperature positions. Both are to the footprint like any other layer; the selection is a temperature-and-arc decision that overrides the dielectric numbers. [10]

Are these materials "UL 1446 qualified"?

No single layer is, and no honest supplier will claim otherwise. UL 1446 qualifies an insulation SYSTEM, the tested combination of paper, film, varnish, and winding, and the thermal class belongs to that qualified system. What each converted layer carries is its own documentation: its thermal class, its dielectric strength, its test methods, and lot-code traceability. The layer supports a qualified system; it does not carry the qualification alone. A substitution, even like-for-like, is a system decision. [12]

Which switchgear standard governs my creepage and clearance?

It depends on voltage and region. Low-voltage assemblies follow IEC 61439 (with the creepage/clearance principles from IEC 60664-1); medium- and high-voltage switchgear follows the IEC 62271 family; North American metal-clad MV gear follows the ANSI/IEEE C37 series, including IEEE C37.20.2. The barriers and supports on this page are built into those listed assemblies, so their material and geometry are constrained by the assembly's verification, not chosen in isolation. Verify the governing edition before final spec. [13]

Does H-O mold or extrude these insulators, or convert them?

H-O and converts sheet, roll, and laminate stock to drawing, and kiss-cut barriers, slit films and papers, machined and laminate supports, and kitted coil-insulation sets. We do not mold or extrude these parts; molded and extruded profiles are coordinated through a partner network. Conversion runs in Winsted, Connecticut under an ISO 9001:2015 certified quality management system with material traceability and lot-code TDS records.

What should I put on the drawing set so the quote comes back right the first time?

The three axes plus the mechanics: the voltage class and rated impulse voltage (Uimp), the pollution degree, the winding hotspot or target thermal class, the dielectric-strength target or governing creepage/clearance, and, for supports, the fault current and bolt pattern.

Add the barrier or wrap geometry and gauge, any adhesive or liner needs, quantities for prototype and production, and the standards language you need on the paperwork (material classes and dielectric strength per TDS; insulation system by designation). "Recommend the layer" is a valid callout: that is what the engineering review is for.

Definitions

Glossary: terms used on this page

Quick reference for the thermal-class, dielectric, and creepage terminology used throughout. Each entry links to the relevant standard or test method where applicable.

Thermal class / Class R (220 C)

The continuous hotspot temperature an insulation is designed to withstand for its rated life, per IEC 60085 [1]. The letters run A 105, B 130, F 155, H 180, N 200, R 220 °C; Class R is the current top designation, and aramid paper is its backbone.

Creepage

The shortest path along the surface of an insulator between two conductive parts. Under pollution the surface path governs, and the required distance comes from IEC 60664-1 [2] (LV) or IEC 62271 (MV), set by the impulse voltage, pollution degree, and material group.

Clearance

The shortest straight-line distance through air between two conductive parts. Distinct from creepage: creepage ≥ clearance because the surface path is longer, and under pollution creepage is usually the limiting distance.

Comparative tracking index (CTI)

A measure of how well an insulator surface resists tracking, per IEC 60112 [3]. It sorts materials into groups that set the required creepage: a high-CTI surface needs less creepage for the same voltage and pollution degree.

Dielectric strength

The electric field a material withstands before breakdown, in kV/mm, per ASTM D149 [5] or IEC 60243. Measured on clean, flat material, so working margin allows for folds, edges, and thin spots.

Pollution degree

A rating (PD1–PD4, per IEC 60664-1 [2]) of the conductive contamination expected on an insulator surface; an industrial panel or switchboard is typically PD3. Heavier pollution raises the required creepage.

NEMA LI 1 / G-10 / FR-4

The industrial-laminate classification (NEMA LI 1 [6]) that defines the glass-epoxy grades G-10, flame-retardant FR-4, and G-11 used as load-bearing busbar supports, standoffs, and phase barriers.

Vulcanized fibre / fish paper

Cellulose treated with zinc chloride, then washed and pressed into a tough insulating sheet with roughly 6–10 kV/mm dielectric strength ([11]). The classic LV slot-liner, washer, and end-lamination material; cleanly without fraying.

Aramid paper (Nomex)

Meta-aramid paper (Nomex® 410 calendered, 411 uncalendered) with outstanding thermal endurance and mechanical strength; the 220 °C (Class R) backbone for transformer layer, coil, and lead insulation.

Insulation system (UL 1446)

The qualified combination of paper, film, varnish, and winding evaluated together per UL 1446 [12]. The thermal class belongs to the system, so a substitution is a system decision; a single layer supports the system without carrying its qualification.

Relative thermal index (RTI)

A material's long-term thermal-ageing rating, per UL 746B [8]; part of the qualification package for demanding film positions such as PEEK.

Rated impulse voltage (Uimp)

The peak transient (lightning/switching) voltage the insulation must withstand; one of the inputs, with pollution degree and material group, that sets the required creepage and clearance in the IEC 60664-1 [2] tables.

Last updated · Reviewed by H-O Products engineering (ISO 9001:2015 certified converter, Winsted, CT).

Citations

Standards, test methods & technical references

The standards, test methods, and maker technical data sheets cited throughout this page. The insulation-system framework (UL 1446) is cited by designation: it qualifies the tested paper/film/varnish combination, and the class belongs to the qualified system. Standards editions current as of July 2026; verify against the publishing body before final spec. H-O materials are aligned to these standards through the source manufacturer's TDS, not independently certified by H-O unless explicitly stated on the quote.

[1] IEC 60085

Electrical insulation — Thermal evaluation and designation. The thermal-class framework (A 105 / B 130 / F 155 / H 180 / N 200 / R 220 °C) used throughout the transformer and coil sections of this page. webstore.iec.ch (IEC 60085)

[2] IEC 60664-1

Insulation coordination for equipment within low-voltage supply systems, Part 1: Principles, requirements and tests. The source of the creepage and clearance tables, pollution degrees, and material groups that frame this page's distances. webstore.iec.ch (IEC 60664-1)

[3] IEC 60112

Method for the determination of the proof and the comparative tracking indices of solid insulating materials. The CTI method behind the material groups; cited on the Durostone® composite TDSs. webstore.iec.ch (IEC 60112)

[4] IEC 60243

Electric strength of insulating materials, Test methods. The breakdown-gradient method behind the kV/mm values on the composite and film TDSs cited here (Durostone® EPC 203: 16 kV/mm per TDS). webstore.iec.ch (IEC 60243)

[5] ASTM D149

Standard Test Method for Dielectric Breakdown Voltage and Dielectric Strength of Solid Electrical Insulating Materials at Commercial Power Frequencies. The method cited on the polyimide, PEEK, aramid, and fibre TDSs referenced here. astm.org (D149)

[6] NEMA LI 1

Industrial Laminating Thermosetting Products. The grade system that defines G-10, FR-4, and G-11, the designations for the glass-epoxy busbar supports and phase barriers on this page. nema.org (LI 1)

[7] UL 94

Standard for Tests for Flammability of Plastic Materials for Parts in Devices and Appliances. The flame-class listings cited on the ManniGlas®, G10/FR4, and Durostone® TDSs. shopulstandards.com (UL 94)

[8] UL 746B

Polymeric Materials, Long Term Property Evaluations. The long-term thermal-ageing evaluation (RTI) cited on the PEEK (APTIV®) TDS, part of the qualification package for demanding film positions. shopulstandards.com (UL 746B)

[9] Durostone® composite TDS

Manufacturer technical data sheets for the Durostone® composite grades cited on this page (electric strength per IEC 60243, tracking per IEC 60112, thermal endurance per IEC 60216, UL 94 listings; EPC 203 reports 16 kV/mm). Roechling technical library; verify the current grade sheet before final spec.

[10] Film, paper & barrier maker literature

Manufacturer technical libraries for the Nomex® and Kapton® families, Apical® polyimide, APTIV® PEEK film, mica barrier sheet, ManniGlas® glass-fiber paper, and ArmaGel® aerogel; gauge ranges, grade naming, temperature ratings, and test methods per the published data sheets. Values per the TDS on file for the selected grade.

[11] Vulcanized fibre / fish paper (NEMA F/FR)

Electrical-grade vulcanized fibre / fish paper: cellulose treated with zinc chloride; dielectric strength roughly 6–10 kV/mm (about 150–250 V/mil by gauge); NEMA F and NEMA FR grades. Values per the supplier data sheet on file; dielectric strength per ASTM D149. Verify grade and gauge before final spec.

[12] UL 1446

Standard for Systems of Insulating Materials, General. The system-qualification framework for the paper / film / varnish combinations inside transformers and machines; the reason substitutions are system decisions and the class belongs to the qualified system. shopulstandards.com (UL 1446)

[13] IEEE C37.20.2 / IEC 61439 / IEC 62271

The switchgear-assembly standards (IEEE C37.20.2 for metal-clad MV gear; IEC 62271 for HV/MV switchgear; IEC 61439 for LV assemblies) that the supports and barriers on this page are built into. Material selections inside a listed assembly are constrained by its verification. standards.ieee.org

Updated . Standards editions and links current at publication; verify against the publishing body before final spec. H-O converts materials aligned to the methods cited; H-O does not certify insulation systems. Lot-specific documentation available on request.

What to send H-O

To review your distribution-insulation design, send:

  • Voltage class & rated impulse voltage (Uimp)
  • Pollution degree (PD1–PD4)
  • Winding hotspot / target thermal class
  • Dielectric-strength target or governing creepage/clearance
  • Fault current & bolt pattern (for supports)
  • Barrier / wrap geometry & gauge
  • Adhesive / liner / lamination needs
  • Prototype and annual volume
Quote request

Get a power-distribution insulation engineering quote

Send a drawing set, winding spec, or cubicle layout. We typically respond within one business day with a material recommendation, prototype lead time, and TDS verification against your thermal class, dielectric margin, and creepage/clearance.

Contact
Company address
Your application
Part & quantity
Typical response in one business day. Samples typically 3–5 business days; production in about 2 weeks. MOQ varies by material and part. Expedited service available.

Material data & standards. All thermal-class, dielectric, and temperature values on this page are taken from the source maker's technical data sheets with the method named (ASTM D149; IEC 60085, 60664-1, 60243, 60112, 60216; NEMA LI 1; UL 94, UL 746B classes per the listed grade TDSs).

The insulation-system framework (UL 1446) and the switchgear-assembly standards (IEC 62271, IEC 61439, IEEE C37.20.2) are cited by designation only: they qualify systems and assemblies, the class or listing belongs to the tested combination, and the materials on this page support designs evaluated to them.

H-O converts materials; H-O does not qualify insulation systems or certify switchgear, and does not independently certify materials against the standards unless explicitly stated on the quote. Verify against the maker TDS and your system-level qualification plan.

Conversion scope. H-O and converts sheet, roll, and laminate stock to drawing in Winsted, Connecticut: die-cut and kiss-cut barriers, slit films and papers, machined and laminate supports, waterjet-cut thick sections, laminations, and kitted coil-insulation sets, with material traceability and lot-code TDS records. H-O does not mold or extrude these parts; molded and extruded profiles are coordinated through a partner network. Lead-time and MOQ details are in the process strip and the quote form above.

Get Quote →